Page 5
5 rotary actuators, Lead / Lag control, Touch Screen Human Machine Interfaces (HMI), ModBUS communications and other advanced features. These features make the LMV5 extremely flexible, and ideally suited for use with most steam boilers, hot water boilers, thermal fluid heaters, and industrial burners.
Page 6
One HMI can be used to interface with multiple AZL5s. The HMI is not necessary for operation of the base unit. LMV5 QSG Rev 4 Sec 1 Pg 2 www.scccombustion.com...
Page 7
0.06” parallel misalignment with no appreciable side load. Note: SCC never recommends soild couplings. Flame Detector Options and Accessories (The LMV5 does not require a flame signal amplifier) QRI2A2.B180B Sensor is self checking, forward viewing (IR) detector (continuous use) AGG2.110 3/4"...
Page 8
100 ohm 3 wire platinum RTD, with aluminum weather head Needed for water temperature 4” insertion, spring loaded probe, 1/2” NPT SS thermowell 3/4” NPT conduit connection, terminal connections Range -40 to 900 LMV5 QSG Rev 4 Sec 1 Pg 4 www.scccombustion.com...
Page 9
Includes 3 finger speed wheel (Standard speed) 6 ft cable Range 300 to 6300 RPM ADPT-6F Optional 6 finger speed wheel (Low speed) Used with the AGG5.310 kit above Range 150 to 3150 RPM LMV5 QSG Rev 4 Sec 1 Pg 5 www.scccombustion.com...
Page 10
At least one is required on each BMS Additional transformers may be necessary depending on the number of actuator / modules FUSE6.3A-SLOW 6.3A 250V 5x20mm Slo-Blow Qty (10) LMV5 primary FUSE4.0A-SLOW 4.0A 250V 5x20mm Slo-Blow Qty (10) LMV5 secondary AGG5.643...
Page 12
Protection against electrical shock hazard on the LMV5, and on all connected electrical components must be ensured through good wiring and grounding practices. Fall or shock can adversely affect the safety functions of an LMV5. Such units must not be put into operation, even if they do not exhibit any apparent damage.
Page 17
It should be noted that the mounting screws do not have excessive play, so the spacing of the mounting holes must be accurate. This can be easily achieved by placing the LMV5 in the desired position and turning each of the mounting screws to mark the plate that the LMV5 will be mounted to.
Page 18
AZL5 is mounted, but does require approximately 2.5” below the bottom of the AZL5 to clear the connector and the CANbus cable. Please see Section 10-1 for specifications. Figure 2-2.1 AZL5 Dimensions (inches) LMV5 QSG Rev 4 Sec 2 Pg 2 www.scccombustion.com...
Page 19
SQM4x Actuators 2-3 The SQM4x actuators that are driven by the LMV5 come in three basic torques and running times as described in the product offering. See Section 1-2. Actuators can rotate clockwise or counterclockwise depending upon programming in the LMV5.
Page 20
PLL52 (if equipped). This transformer should also be mounted in an enclosure that shields the transformer from dirt and water. At least one transformer is necessary for each LMV5 base unit. Depending upon how many devices are connected to the CANbus, (actuators, PLL52 module, etc) two AGG5.210 transformers may be necessary.
Page 21
UV scanner is used instead of the IR scanner. Liquid tight conduit can be mounted to the back of the QRI scanner with adapter (AGG2.120). Please see Section 10-1 for specifications. Figure 2-4.2 QRI Dimensions (inches) LMV5 QSG Rev 4 Sec 2 Pg 5 www.scccombustion.com...
Page 22
Glowing refractory is well tolerated by the UV scanner. A 12 ft pre-made cable must be used. Please see Section 10-1 for specifications. Figure 2-4.3 QRA75 Dimensions (inches) LMV5 QSG Rev 4 Sec 2 Pg 6 www.scccombustion.com...
Page 23
A small LB is included on the back of the sensor for connecting conduit and for making electrical terminations. Note: The QAE2020.005 is a replacement for the discontinued 556-541. Please see Section 10-1 for specifications. Figure 2-4.5 QAE2020.005 Dimensions (inches) LMV5 QSG Rev 4 Sec 2 Pg 7 www.scccombustion.com...
Page 24
The ratings of these sensors are given in Section 1. Stack and ambient temperature sensors are necessary if the efficiency is monitored by the LMV52. A water jacket sensor is recommended if the LMV5’s low fire hold functionality is used on a steam boiler. Figure 2- 4.6 Stack Sensor Dimensions (inches) RBF195M482-010-00-8HN31 Figure 2- 4.7 Water Jacket Sensor Dimensions (inches)
Page 26
After welding, the QGO20 can be inserted and bolted to the flue gas collector flange. Please see Section 10-1 for specifications. Figure 2-5.3 Flue Gas Collector dimensions (inches) LMV5 QSG Rev 4 Sec 2 Pg 10 www.scccombustion.com...
Page 28
The speed wheel can be reversed (flipped over) so that the arrow on the speed wheel points in the correct direction of motor rotation. The shoulder bolt should be tightened with about 50 in*lb (6 Nm) of torque. LMV5 QSG Rev 4 Sec 2 Pg 12 www.scccombustion.com...
Page 29
Matchmark the sensor, install the lockwasher and locknut, and tighten the locknut without rotating the sensor. Zip tie the sensor wire to the motor, if desired. (For wiring, see Section 3) LMV5 QSG Rev 4 Sec 2 Pg 13 www.scccombustion.com...
Page 33
Each plug is designed to connect one external device or a small group of external devices, such as gas valves, to the LMV5. This being the case, each group of plugs on the front of the LMV5 provide line voltage and grounds so that an additional terminal strip is not necessary.
Page 34
The sole purpose of the FE is for termination of low voltage cable shields. The FE is bonded to the Reference Ground through capacitors on the LMV5 circuit board with the exception of the CANBus where it is bonded directly.
Page 35
It is extremely important that the shield of the CANBus cable is properly terminated. The shield of the CANBus cable is terminated to the LMV5 by using a special strain relief, part number AGG5.110. This strain relief also has a wire that should be connected to the shield terminal on the LMV5.
Page 36
PLL52 Module) so that the entire shield has continuity with terminal X51.1 which is the shield connection on the LMV5. This is achieved by clamping the shield on both cable segments with the metal clamps provided on the cable entry of each actuator. Clamps for the CANBus shield are also provided on the PLL52 module.
Page 37
W2 will be used if the dry contact is closed. If the LC is in mode 1A, 1B, 3, 4, 5, or 6, and the dry contact is closed, the LMV5 will revert back to mode 2 and will use setpoint W1.
Page 39
Programable Pin3 Air Pressure Switch Test, if direct start is used 0.5A, 120V Output (Start/PS-Valve, ContinuousPurge, NormDirectStart) Note: Total combined load of all of all 120VAC outputs cannot exceed 5 amps. LMV5 QSG Rev 4 Sec 3 Pg 7 www.scccombustion.com...
Page 40
Start RelGas, CPI Oil, CPI Gas, or CPI Gas+OIL Programable LMV52 Pin 2 1.6 mA, 120V Note: CPI, Closed Position Indicator = POC, Proof Of Closure Input Only (StartReleaseGas) Pin 3 Line 500mA, 120V Line LMV5 QSG Rev 4 Sec 3 Pg 8 www.scccombustion.com...
Page 41
See Note: Main Gas Valve V1 Upstream main gas valve Note: If a X9-01 Pin 4 non-Siemens gas valve is used, that draws more than 1.6A, Pin 4 Output a separate safety relay must be used to power the gas valve. If valve proving is used, V1 and V2 must be wired separately.
Page 42
Figure 3-2.5 LMV5 Top Terminals X50 thru X52 Layout LMV5x Description / Notes Type Rating Terminal Pin 1 CANbus Shield (clamp to shielding of the cable) Pin 2 12VAC1 Power for the AZL Power 12 VAC, 4A Pin 3 12VAC2 Power for the AZL...
Page 57
Section 4 Parameters Parameters Introduction 4-1 The Siemens LMV5 BMS has a number of parameters (settings) that can be adjusted to suit the wide variety of applications that exist in the burner / boiler and industrial heating market. These parameters are broken up into three main groups by password access.
Page 58
Typical Settings Although the LMV5 has many parameters that can be adjusted, most burners / boilers only need a few parameters adjusted to operate properly. If the burner / boiler has been shop tested, the number of parameters that must be adjusted is reduced even further.
Page 59
The LMV51 has many more capabilities than what is listed above, and the LMV52 has many more capabilities than the LMV51. In order to make its many features user friendly, an LMV5 Parameter worksheet was created. This worksheet is Section 4-2 and carries all pertinent information concerning the parameters of the LMV5.
Page 60
If attempted, memory can be permanently damaged. An AZL52 can be used on any LMV5, (LMV51, LMV52 ) with no problems. The parameter set that the LMV5 uses for operation is stored in the LMV5 itself. When a parameter is changed (via the AZL5 or ACS450), the actual change in memory (parameter set) occurs in the LMV5 and not the AZL5.
Page 61
Press Enter, and the parameter set will be written from LMV5(Z) to AZL5(Z). Note: The AZL5(Z) does not need to be blank. The BurnerID in the LMV5 will overwrite it. An LMV5 will always overwrite the BurnerID in the AZL5.
Page 62
Setting Fuel Trains A number of different fuel train options exist for the LMV5. There are several trains for gas and several trains for oil. The following schematics describe the various options available for parameters (FuelTrainGas and FuelTrainOil). For gas, Pilot GP2 is normally used. For Light Oil, LO w Gasp is normally used.
Page 63
Gas valve V2 (Main, dwn. stream) X4-02.3 Ignition X9-01.1 Gas valve SV (Usually Outdoor) X9-01.2 Gas valve PV (Pilot Valve) X9-01.4 Gas valve V1 (Main, up stream) X9-01.3 Gas valve V2 (Main, dwn. stream) LMV5 QSG Rev 4 Sec 4 Pg 7 www.scccombustion.com...
Page 64
(other trains possible) Figure 4-1.8 : Gas pilot ignition for light oil, staged or modulating (other trains possible Figure 4-1.9 : Gas pilot ignition for Heavy oil, modulating (other trains possible) LMV5 QSG Rev 4 Sec 4 Pg 8 www.scccombustion.com...
Page 65
Oil valve V1 (Main) Safety Time 2 HO ONLY X4-02.3 Ignition X9-01.1 Gas valve SV (Usually Outdoor) X9-01.2 Gas valve PV (Pilot Valve) X8-02.1 Oil valve V1 (Main) X8-03.1 Oil valve V1 (Main) LMV5 QSG Rev 4 Sec 4 Pg 9 www.scccombustion.com...
Page 66
Addressing SQM4 Actuators Before actuators can be operated by the LMV5 they must be addressed and the direction or rotation must be set if it was not previously set. Depending on direction of rotation and home position set in the LMV5, the actuator may rotate as soon as it is addressed.
Page 67
Note: Check rotation of ALL actuators BEFORE commissioning combustion curves. This includes the oil actuator BEFORE commissioning the combustion curves on gas. If the direction of rotation is changed for any actuator, ALL combustion curves (both fuels) MUST be deleted. LMV5 QSG Rev 4 Sec 4 Pg 11 www.scccombustion.com...
Page 68
After the special positions are set, the burner can be lit-off. Please see below for the recommended light off procedure. The LMV5 can hold the burner in the pilot phase (Interval 1, phase 44) as well as a number of other phases with the “Program Stop” function. See parameter worksheet under Params & Display >...
Page 69
On most new installations, the Fuel-Air ratio curves are not set by the burner OEM, and must be set at start-up. If this is the case, the LMV5 will automatically set Point 1 (low fire) to the ignition position that was previously set. Point 1 can be changed without changing the ignition position if a low fire different from ignition is desired.
Page 70
If points are deleted from an existing curve, the reverse of what was previously explained happens. Although not recommended, a curve could consist of two points. One point at low fire and one point at high fire. The LMV5 would simply draw a line between the two points and that would be the combustion ‘curve’.
Page 71
External Load Control ExtLC Bus control via ModBUS via ModBUS * Bumpless transfer (LMV5 will not cycle off) occurs, from Mode 5 > Mode 2, or Mode 2 > Mode 5. LMV5 QSG Rev 4 Sec 4 Pg 15 www.scccombustion.com...
Page 72
MaxTmeMod should be set to a high number (30 min) so that it has no effect. 3. Time based stepping start The LMV5 will be held at low fire until a certain time elapses, and then a step-up in load will be taken. This continues until the ThresholdOFF value is reached.
Page 74
Special Features In addition to the capabilities mentioned above, the LMV5 also has many special settings that are very useful in some situations. These special settings are detailed in the next section, section 4-2. This section details the special settings (parameters) that are used most frequently. These are: NumFuelActuators Permits the LMV5 to run dual fuel with a single actuator.
Page 77
StartRelease, 33 Note: The Parameters shown in bold type must be set in an ReacExtranLight, 30 StartRelease Gas/Oil, 28 unprogrammed LMV5. See section 4, table 4-1.1 Release Stages, 46 State O2 Ctrl, 42 typ* -(Typical) Parameter occurs on pages: 34,51,52,54,55...
Page 78
Set the Date, 2 formats are offered MM-DD-YY (optional) DD.MM.YY (default) Date Operation> Select format at: Params & Display>AZL>DateFormat Date/TimeOf Day> TimeOfDay Set the Time Of Day. 24 hour format : HH:MM Set Clock Weekday Set the Weekday. LMV5 QSG Rev 4 Sec 4 Pg 22 www.scccombustion.com...
Page 79
This enables or disables Com 2, the RJ45 jack on the back of the AZL, for ModBus or eBUS communication. OptgMode Select GatewayBASoff This port uses RS-232 communications. Type of Gateway This parameter configures the protocol of Com 2. Options are ModBus or eBUS LMV5 QSG Rev 4 Sec 4 Pg 23 www.scccombustion.com...
Page 80
After a safety related shutdown of the LMV, instead of the normal PrepurgeTmeGas (Oil), PrepurgeSafeGas or this prepurge time is used for the next LMV start-up. PrepurgeSafeOil Range = longer than MinT_PrepurgeGas (Oil) to 63min Def = 20 sec Typ = By OEM LMV5 QSG Rev 4 Sec 4 Pg 24 www.scccombustion.com...
Page 81
Most critical safety time other than prepurge. Shorter times are more safe. Range = 0.2 to 10 sec, 15 sec for oil Def = 3 sec Typ = 5 sec LMV5 QSG Rev 4 Sec 4 Pg 25...
Page 82
(not done in the US). This time period will double after the first relight attempt. This doubling would occur if the RepetitCounter were set to 3 or greater. Range = MinTmeHomeRun to 63sec Def / Typ = 10 sec LMV5 QSG Rev 4 Sec 4 Pg 26 www.scccombustion.com...
Page 83
When Magnetcoupl is selected, this setting determines when terminal X6-02.03 is energized. Def = on in IgnOilPumpStart Ph22, Typ = on in Ph38, Note: If a direct spark oil train is selected, spark will occur during prepurge if set to 22-38 Ph22. LMV5 QSG Rev 4 Sec 4 Pg 27 www.scccombustion.com...
Page 84
Phase 21, and if it de-energizes at any time after, it will cause a lockout. This is usually wired to a atomizing StartReleaseOil media pressure switch. A temperature switch may also be placed here for heavy oil. Can be deactivated. Def / Typ = Activated LMV5 QSG Rev 4 Sec 4 Pg 28 www.scccombustion.com...
Page 85
Deact x OGP is only offered on the LMV52. Activates or deactivates (INPUT X9-03.03) for a high gas pressure switch. GasPressureMax Most gas fired installations require high a gas pressure switch. Def = Activated LMV5 QSG Rev 4 Sec 4 Pg 29 www.scccombustion.com...
Page 86
Activates or deactivates the extraneous light check during the start sequence and during standby. NOTE : ExtranLightTest This setting is intended to be used with applications such as waste incinerators. DO NOT deactivate for boiler burners. Def = Activated LMV5 QSG Rev 4 Sec 4 Pg 30 www.scccombustion.com...
Page 87
The LMV will alarm when this value is less than about 16%. Not adjustable. Flame signal range is 0-100% Flame failure is at 16% (raw) Extraneous light is at 4% (raw) LMV5 QSG Rev 4 Sec 4 Pg 31 www.scccombustion.com...
Page 88
For the LMV52, this defines how the main flame for oil firing is supervised. Options 1 thru 7 as described in SensOperPhOil 60-62 parameter SensExtranlGas and SensPilotPhGas also apply to this parameter. Def = 1 Sensor LMV5 QSG Rev 4 Sec 4 Pg 32 www.scccombustion.com...
Page 89
VP_Tme_GasPress downstream valve is leaking and the LMV will lockout. A longer time period will produce a more sensitive test. Range = 10 to 63 sec, Def / Typ =10 sec LMV5 QSG Rev 4 Sec 4 Pg 33 www.scccombustion.com...
Page 90
Range = 0º - 90º Def = 90º Typ = at least 2º from valve / damper mechanical stops. Sets the prepurge position of the VSD. PrepurgePosVSD Range = 10 to 100% Def = 100% Typ = At least 60%. LMV5 QSG Rev 4 Sec 4 Pg 34 www.scccombustion.com...
Page 92
If a O2 sensor is attached and activated, (LMV52) the O2 value will also be displayed on the screen. Params & Display> When a specific point is selected (Point 2 for example) the LMV5 will prompt if the point is to be changed or CurveParams CurveParams Ratio Control>...
Page 93
The only actuator that can be changed on LMV51 is the Aux Actuator. GasActuator StartPoint Op - This parameter controls what curve point the LMV5 drives to in Phase 54. The LMV releases to this curve point, typically point 1 ( OilSettings >...
Page 94
Note: auto deact - This status will appear when the O2 control deactivates itself, due to an operating fault or componenent malfunction. If the control goes into auto deact, it has to be reactivated under: Operation > O2Ctrl activte . LMV5 QSG Rev 4 Sec 4 Pg 38 www.scccombustion.com...
Page 95
Tau High-Fire - Range = 1 to 27 sec, Def = invalid (must be set automatically) Tau Low-Fire OEM - Range = 1 to 27 sec, Def = invalid (can be set manually) Tau Low-Fire LMV5 QSG Rev 4 Sec 4 Pg 39 www.scccombustion.com...
Page 96
Adjustable constants for calculating the combustion efficiency when firing gas. A2 -- Range = 0.40 to 80 Def = 0.65 Typ = 0.65 B/1000 -- Range = 1 to 20 Def / Typ = 9 B / 1000 LMV5 QSG Rev 4 Sec 4 Pg 40 www.scccombustion.com...
Page 97
O2 ratio control curve. When the LMV has compensated as much as possible for a lean condition, value will be about 15%, and as much as possible for a rich condition, value will be about 52%. LMV5 QSG Rev 4 Sec 4 Pg 41...
Page 98
1 = the load controller is in auto-tune Diag Reg State 2 = the O2 sensor is being tested for response (the LMV5 does this periodically during operation) 3 = the fuel air ratio curves or the O2 trim curves are being programmed.
Page 99
PI loop. If "canned" values are not used 15 seconds is usually a good starting point. Range = 0 to 1000sec Def = 40sec Typ = 24sec LMV5 QSG Rev 4 Sec 4 Pg 43 www.scccombustion.com...
Page 100
Set at a negative %, so that the burner will turn on stage1 at a set % below the current setpoint. The % is based on the current setpoint. Range = -50 to +50%, Def / Typ = -2% LMV5 QSG Rev 4 Sec 4 Pg 44...
Page 101
TL_Thresh_Off LMV5 faults, and does NOT lockout. LMV5 re-starts when temperature goes below TL_SD_On. Params & Display> This is normally used to prevent hot water boilers from exceeding their design temperatures.
Page 102
Range = 0 to 842 degrees F Def = 140 Typ = 300 For staged burners, this enables or disables stages (other than the first stage) to be released during a cold Release Stages start. LMV5 QSG Rev 4 Sec 4 Pg 46 www.scccombustion.com...
Page 103
4) N S 4) No Sensor - Selected if LMV5x being remotely modulated, no sensor for the load controller t d if LMV5 b i d l t d th l t ll or the temperature limiter.
Page 104
Selects the output signal to be either a 0 to 20mA signal or a 4 to 20mA signal. CurrMode 0/4mA Range = 0 to 20mA or 4 to 20mA Def = 0 to 20mA Typ = 4 to 20mA LMV5 QSG Rev 4 Sec 4 Pg 48 www.scccombustion.com...
Page 105
This load is used to determine the thermal response of the system during Adaption only. LMV will travel to this load during the heating phase of the Adaption. AdaptionLoad Range = 40 to 100% Def / Typ =100 LMV5 QSG Rev 4 Sec 4 Pg 49 www.scccombustion.com...
Page 106
W3 is the ModBus conveyed setpoint. Range = 0 to 3632 degrees F or 1500 PSIG Params & Display> < > Display Contrast Change with keys store with Enter key, cancel with the Esc key. LMV5 QSG Rev 4 Sec 4 Pg 50 www.scccombustion.com...
Page 107
4 AuxActuator1 These descriptions are opposite if viewed from the cover end of the actuator. (shaft pointing away from you) 5 AuxActuator2 Range = Standard, Reversed Def = Standard 6 AuxActuator3 LMV5 QSG Rev 4 Sec 4 Pg 51 www.scccombustion.com...
Page 108
2 Gas Actuator(Oil) Params& Display> 3 Oil Actuators Actuator> Information concerning the software versions of the attached actuators. 4 Aux Actuators 1 SW Version 5 Aux Actuators 2 6 Aux Actuators 3 LMV5 QSG Rev 4 Sec 4 Pg 52 www.scccombustion.com...
Page 109
The number of speed deviations exceeding 0.5% of the speed setpoint during a VSD run period. Absolute Speed This displays the real time speed of the blower motor in RPM (tachometer). LMV5 QSG Rev 4 Sec 4 Pg 53 www.scccombustion.com...
Page 110
This measures the resistance of the O2 sensor. As a sensor is used, the resistance increases. New sensors have a resistance of 0 ohms. QGO Resistance When this value exceeds 100 ohms, sensor should be replaced the next time the burner is serviced. Absolute maximum is 150 ohms. LMV5 QSG Rev 4 Sec 4 Pg 54 www.scccombustion.com...
Page 111
For oil firing, this sets the time that must elapse before the Aux 3 actuator is released to modulate. DelaytimeFGR Oil Has no effect if parameter "FGR-Mode" is set to temperature. Range = 0 to 63 minutes. Def = 300 seconds. Typ = 30 minutes LMV5 QSG Rev 4 Sec 4 Pg 55 www.scccombustion.com...
Page 112
See: Params & Display > LoadController > Configuration > Analog Output > OutValueSelection Sets the allowable differernce between channels A and B of the Actuator's Potentiometer. allowed Pot.Diff Range = 10 to 15. Def / Typ = 10 LMV5 QSG Rev 4 Sec 4 Pg 56 www.scccombustion.com...
Page 113
Burner ID must be set here. The burner ID can only be changed if be changed with OEM Access. Generally, Updating Burner ID the burner / boiler serial number is used. Range = 4-15 char ,Def = Invalid LMV5 QSG Rev 4 Sec 4 Pg 57 www.scccombustion.com...
Page 114
NOTE : Each burner must have a UNIQUE burner ID for safety purposes. NOTE : When Updating> transferring parameter sets from the AZL to the LMV5 do not stop the transfer until "Backup Restore transferring parameter sets from the AZL to the LMV5, do not stop the transfer until Backup Restore Param Backup AZL ->...
Page 115
When the: Operational Stat > Normal Operation screen is displayed, Actuator positions (Only the Enter key can be pressed, one additional time, so that the actuator positions on LMV52) of all devices (O2 module VSD etc..) will be displayed. LMV5 QSG Rev 4 Sec 4 Pg 59 www.scccombustion.com...
Page 116
Sequence Diagrams 4-3 The Siemens LMV5 BMS can perform a number of different burner sequences based upon how certain parameters are set. Although there are a number of parameters that affect small aspects of the burner sequence, the main parameters that affect the sequence are parameters FuelTrainGas or FuelTrainOil.
Page 117
11) If direct start is enabled and there is a call for heat after phase 62, the LMV5… will omit phase 78 and will go to phase 79. In Phase 79, the LMV5… will check the blower air pressure switch with the blower still running by using a three-way solenoid valve (APS checking).
Page 118
Gas valve V2 (Main, dwn. stream) Legend : Energized Must be Energized by end of Phase See the first pages of Section 4-3 for notes. Energized or De-energized Must be De-energized by end of Phase De-energized LMV5 QSG Rev 4 Sec 4 Pg 62 www.scccombustion.com...
Page 119
Gas valve V2 (Main) Legend : Energized Must be Energized by end of Phase See the first pages of Section 4-3 for notes. Energized or De-energized Must be De-energized by end of Phase De-energized LMV5 QSG Rev 4 Sec 4 Pg 63 www.scccombustion.com...
Page 120
Gas valve V2 (Main, dwn. stream) Legend : Energized Must be Energized by end of Phase See the first pages of Section 4-3 for notes. Energized or De-energized Must be De-energized by end of Phase De-energized LMV5 QSG Rev 4 Sec 4 Pg 64 www.scccombustion.com...
Page 121
Oil valve V3 (Staged, load depen.) Legend : Energized Must be Energized by end of Phase See the first pages of Energized or De-energized Must be De-energized by end of Phase Section 4-3 for notes. De-energized LMV5 QSG Rev 4 Sec 4 Pg 65 www.scccombustion.com...
Page 122
Oil valve V3 (Staged, load depen.) Legend : Energized Must be Energized by end of Phase See the first pages of Energized or De-energized Must be De-energized by end of Phase Section 4-3 for notes. De-energized LMV5 QSG Rev 4 Sec 4 Pg 66 www.scccombustion.com...
Page 123
Oil valve V3 (Staged, load depen.) Legend : Energized Must be Energized by end of Phase See the first pages of Energized or De-energized Must be De-energized by end of Phase Section 4-3 for notes. De-energized LMV5 QSG Rev 4 Sec 4 Pg 67 www.scccombustion.com...
Page 124
See the last pages of section 4-1 for notes. Legend : Position not checked Ignition Position U Undefined Position M Actuators Modulating H Home Position S Actuators Stopped T Actuators Transitioning PsP Postpurge Position LMV5 QSG Rev 4 Sec 4 Pg 68 www.scccombustion.com...
Page 127
1) The wiring on the AGG5.210 transformer, specifically how the four pin connector X52 is wired to the LMV5. Most problems occur on Pins 3 and 4 of the transformer. Pin 3 on the transformer and terminal X52.4 on the LMV5 should be wired to PE (Protective Earth or Panel Ground).
Page 128
The second largest category of wiring problems concerns the grounding and the shielding of LMV5 components. The LMV5 has three different types of ground, each with a different function. The three types are: 1) Protective earth or chassis ground (PE)
Page 129
If an analog signal does not exist on the previously motioned terminals when the mode is selected (0 mA when 4-20mA is selected, for example) the LMV5 will fault. See section 3-3 for wiring. If the incorrect mode of load controller is selected for the connected instrumentation or analog signal, the LMV5 will fault.
Page 130
If a cycling switch is placed in this loop, and cycles off, the LMV5 will lockout. 3) If an external load controller (such as a RWF40) is used, or the LMV5 load controller is in any external load controller modes (ExtLC modes 1, 5, 6), then a cycling switch should be put in series with the burner on /off switch wired to X5-03.1.
Page 131
Thus, power will be removed from the high and low gas pressure switch commons when the gas valves open. 4) If terminal X4-01.4 (alarm) is energized when a fault does not exist on the LMV5, this will cause a manual lockout of the LMV5.
Page 132
The QGO20 sensor can take up to two hours to achieve operating temperature on the first start-up. Anytime the LMV5 system / PLL52 has power and parameter O2 sensor is set to activated, the PLL52 will try to maintain the QGO20 at approximately 1292...
Page 133
However, if one input or both inputs are configured for a sensor, (set to Ni1000 or PT1000) and that sensor is not wired in or is not reading, the O2 trim will not activate. LMV5 QSG Rev 4 Sec 5 Pg 7 www.scccombustion.com...
Page 134
“O2 Module not active or not Available”. Check the CANBus wiring to the PLL52 Module. If this wiring is not correct the LMV5 will not auto detect the PLL52 Module. Point must lie 0.5 % O2 above O2 Monitor Curve When setting the O2 Control Curve, messages are received that say “Point must lie 0.5 % O2...
Page 135
When the points on the O2 control curve are set, the LMV5 will prompt at every point with press enter after the O2 value has stabilized. Pressing enter then sets the %O2 for the O2 ratio control curve.
Page 136
Also ensure that the safety loop (X3-04 Pin 1 and Pin 2), and the burner flange (X3-03 Pin 1 and 2) are closed. The LMV5 will not standardize if an alarm is present. Note: When standarization is activated in the LMV52, the air actuator should drive to prepurge position before the run / stop contact closes and the LMV52 puts out 19.5mA.
Page 137
This peak value that is seen should be recorded automatically under: Params & Display > VSD Module >Configuration > Standardized Sp If this doesn’t happen, it’s likely that there’s a problem with the VFD or the speed wheel. LMV5 QSG Rev 4 Sec 5 Pg 11 www.scccombustion.com...
Page 138
VFD caused the LMV52 to alarm by energizing terminal X73.3 on the LMV52 with 24 VDC. Typically, this happens due to an over current in the VFD itself. LMV5 QSG Rev 4 Sec 5 Pg 12 www.scccombustion.com...
Page 139
This is important since these wires are a rich source of EMF (Electromagnetic Field) and can adversely affect the LMV52, causing many different error codes. Metal conduit will contain the vast majority of the EMF. LMV5 QSG Rev 4 Sec 5 Pg 13 www.scccombustion.com...
Page 140
Error RAM test code run Error in connection with data comparison (internal If fault occurs sporadically improve EMC. Any # communication) between µC1 and µC2 If fault occurs continously, replace LMV5 TimeOut during program run synchronization prior to data Internal Fault LMV5 transmission...
Page 141
Fault during voltage supervision test Relay voltage not switched off after reset Fault with devices or wiring connected to the Base Unit (LMV5) Basic unit has detected an improper circuit at one of the outputs, a faulty diode, or a short-circuit in the power supply of Any # the contact feedback network.
Page 142
Display Meaning for the LMV5x system Corrective action code code Fault with devices or wiring connected to the Base Unit (LMV5) Pressure switch gas minimum Pressure switch gas maximum Ignition transformer feedback Fan pressure switch 1) Check connections of the neutrals to all of the Start release oil connected switches, valves, etc...
Page 143
Meaning for the LMV5x system Corrective action code code Fault with Base Unit (LMV5) Ratio Control, O2 Trim, VSD Basic unit has detected a plausibility fault in the ratio control Any # system.The diagnostic code describes the cause of the fault.
Page 144
Display Meaning for the LMV5x system Corrective action code code Fault with Base Unit (LMV5) Any # (Internal) communication error of ELV Detection of different data when making the data comparison Internal Fault If fault occurs sporadically improve EMC. If fault occurs...
Page 145
Ignition position for active fuel actuator not set. Ignition position for aux1 actuator not set. Ignition position for aux2 actuator not set. Ignition position for VSD not set. Ignition position for aux3 actuator not set. LMV5 QSG Rev 4 Sec 5 Pg 19 www.scccombustion.com...
Page 146
LMV5 Actuator 3) Check the two 12V fuses located under black covers Fault Running on the right side of the LMV5 Running time fault of auxiliary actuator 2 Time Aux 4) Check the CANBus power supply (blue or black Actuator...
Page 147
(Set parameter Settling Time to 16) If fault occurs continously, replace LMV5. completed Fault with devices or wiring connected to the Base Unit (LMV5) Limit switches wired into the saftey loop have opened (such as Check all switches wired into the saftey loop circuit. This...
Page 148
Display Meaning for the LMV5x system Corrective action code code Fault with devices or wiring connected to the Base Unit (LMV5) Extraneous Light Any # Basic unit has detected extraneous light during startup on Startup 1) Ensure that the source of extraneous light is not a...
Page 149
Meaning for the LMV5x system Corrective action code code Fault with devices or wiring connected to the Base Unit (LMV5) Flue Gas Recirculation FGR-PS = on, but should have been off 1) Check setpoint on FGR pressure switch. Adjust if Pressure Switch necessary.
Page 150
Meaning for the LMV5x system Corrective action code code Fault with devices or wiring connected to the Base Unit (LMV5) Gas Pressure 1) Bubble test gas valve to ensure that the upstream PS(M)-VP (Pressure Switch Valve Proving) has detected w Valve proving: valve is not leaking.
Page 151
Device Display Meaning for the LMV5x system Corrective action code code Fault with Base Unit (LMV5) Any # Wrong contact position of SR relay If fault occurs sporadically: Improve EMC Any # Wrong contact position of ignition Check wiring on igniton transformer...
Page 152
Meaning for the LMV5x system Corrective action code code Fault with devices or wiring connected to the Base Unit (LMV5) / or Base Unit (LMV5) The time defined by Max SafteyTGas(Oil) is less than Safety time 2 gas too long Internal Fault the time defined by parameter SafteyTmeGas(Oil).
Page 153
(last parameterization was possibly interrupted due to a power damaged 3) If fault cannot be rectified by the reset: Restore failure) parameters form the AZL to the LMV5 4) Replace the LMV5 Page number CRC error of a parameter page...
Page 154
Page has an undefined status 4) Replace the LMV5 Page number Parameter Set Last backup restore invalid (was interrupted) Repeat parameter set download (from AZL to LMV5) damaged Fault when copying a parameter page LMV5 Number of parameter page Fault in connection with EEPROM initialization...
Page 155
Meaning for the LMV5x system Corrective action code code Fault with Base Unit (LMV5) This lockout occurs when escape and enter on the AZL are pressed simutanously. This lockout also occurs Manual Lockout Lockout was made manually via contact Any # when the remote reset X4-01.4 is energized when a...
Page 156
Display Meaning for the LMV5x system Corrective action code code Fault with Base Unit (LMV5) or AZL5 Basic unit has detected wrong state of the internal load Any # controller Fault Feedback If fault occurs sporadically improve EMC. If fault occurs...
Page 157
Display Meaning for the LMV5x system Corrective action code code Fault with Connected actuators, Base Unit (LMV5), or AZL 1) Check CANBus cabling. Ensure that all cable shields Aux 3 Fault Feedback Basic unit has detected a ROM-CRC error (screens) which are located in the cable sheath are Act.
Page 158
3) If fault cannot be rectified by the reset: Restore Invalid parameter access parameters form the AZL to the LMV5 Fault during copying of parameter page 4) Replace the LMV5 External plausibility fault. This type of fault covers possible 1) Check the paramters related to special positions.
Page 159
See diagnostic codes for A1 error codes. These error codes are identical, except they apply to the Aux 1 Actuator. See diagnostic codes for A1 error codes. These error codes are identical, except they apply to the Aux 2 Actuator. Fault with Base Unit (LMV5) Internal Load Controler Internal load controller has detected a fault. Type of fault: See...
Page 160
If fault occurs sporadically improve EMC. If fault occurs CAN error continously, replace LMV5 CAN error CAN error Fault with Sensors Connected to Internal Load Controller, in Base Unit (LMV5) Short-circuit Short-circuit sensor PT100 Terminals X60.1, X60.4 Pt100 Sensor Open-circuit LMV5 Open-circuit sensor PT100 Terminals X60.1 X60.4...
Page 161
Device Display Meaning for the LMV5x system Corrective action code code Fault with Sensors Connected to Internal Load Controller, in Base Unit (LMV5) Open-circuit Open-circuit sensor PT1000 Terminals X60.3, X60.4 PT1000 Sensor Short-circuit Short-circuit sensor Ni1000 Terminals X60.3, X60.4 Ni1000 Sensor Open-circuit Open-circuit sensor Ni1000 Terminals X60.3, X60.4...
Page 162
Meaning for the LMV5x system Corrective action code code Fault with Sensors Connected to Internal Load Controller, in Base Unit (LMV5) Measured value varies too much: PT100 sensor (Terminals X60) Measured value varies too much: PT100 line (Terminals X60) Measured value varies too much: PT1000 (Terminals X60)
Page 163
Display Meaning for the LMV5x system Corrective action code code Fault with Base Unit (LMV5) Internal Load Controler Fault PageAccess, invalid access status Fault voltage monitor test Fault during readout of PDO message XP smaller than min. value XP larger than max. value Internal Fault If fault occurs sporadically improve EMC.
Page 164
>250,000 250,000 Cycles have been exceeded. Internal parts in the startups, Replace LMV5 LMV5.. Are close to the end of their life. service required 1) If fault occurs sporadically: Improve EMC. Internal Fault AZL Save fault parameter 2) If fault occurs constantly: Replace AZL5…...
Page 165
1) If fault occurs sporadically: Improve EMC. 2) If fault occurs constantly: Replace AZL5… EEPROM fault No valid 1) Back up LMV5 pararmeters to AZL. A prompt for this Fault during copying of a parameter page Parameter comes up when exiting the parameters & display menu.
Page 166
1) This indicates that a fault has been relayed to the LMV5 from the VSD via the VSD alarm input terminal. This indicates a fault in the VSD, not the LMV5. Thus, check the VSD error codes and take action based on Alarm from VSD Fault has been triggered by the VSD.
Page 167
Fault with Base Unit (LMV5) VSD Module 1) This indicates that that the LMV5 has decreased its signal to the VSD as much as possible and the motor RPM is still to high. Increase VSD / LMV52 ramp times.
Page 168
3) Check the power supply to the O2 Module 4) Check fuse in the O2 Module Internal Fault O2 If fault occurs constantly, Replace O2 Sensor and / or Fault during calculation test Module Module LMV5 QSG Rev 4 Sec 5 Pg 42 www.scccombustion.com...
Page 169
Module 3) If fault cannot be rectified by the reset: Restore Fault during copying of a parameter page parameters form the AZL to the LMV5 External plausibility fault. This type of fault covers possible 4) Replace the LMV5 faults occurring due to invalid presettings in the drive commands.
Page 170
Meaning for the LMV5x system Corrective action code code Fault with Base Unit (LMV5) or Oxygen Sensor (QGO2..) Any # O2 monitor 1) Check the %O2 between the O2 guard curve and the O2 setpoint curve. Increase the %O2 "gap" between these two curves at the load point where the the fault is occuring.
Page 171
Meaning for the LMV5x system Corrective action code code Fault with Base Unit (LMV5) or Oxygen Sensor (QGO2..) 1) Check mounting of O2 sensor. Ensure no air in O2 Value in entering the stack upstream of the sensor. Operation too...
Page 172
Device Display Meaning for the LMV5x system Corrective action code code Fault with Base Unit (LMV5) or Connected Components Basic unit has detected a ROM-CRC fault in the VSD module Any # Fault Feedback when checking its feedback signal PLL5..
Page 175
O2 control and 11 points for the O2 Ratio Control. The LMV52 does not trim on Point 1, and this is the reason that the O2 Control and O2 Ratio Control curves cannot be set on Point1. LMV5 QSG Rev 4 Sec 6 Pg 1...
Page 176
Cannot trim on Point 1 2909 4218 5527 6836 8145 9455 10764 12073 13382 14691 16000 1.0 % Lean Trim 0.5 % 02 Min Rich O2 Ratio Control O2 Control O2 Monitor Point LMV5 QSG Rev 4 Sec 6 Pg 2 www.scccombustion.com...
Page 177
If this parameter is set to conAutoDeact, the LMV52 will only deactivate the O2 trim, and will continue to function. If the O2 trim automatically deactivates, the actuators will operate on the Fuel-Air Ratio curves that were defined during the Fuel-Air Ratio Control commissioning. LMV5 QSG Rev 4 Sec 6 Pg 3 www.scccombustion.com...
Page 178
O2 CtrlThreshold to the load value (%) of Point 2 or higher if desired. Under Parameters & Display > O2 Contr/Guard > Gas/Oil Settings set LowfireAdaptPtNo 2 (combustion curve point 2) or higher if desired. LMV5 QSG Rev 4 Sec 6 Pg 4 www.scccombustion.com...
Page 179
2) Repeat this process using Method a or b for every point that was defined in the Fuel-Air Ratio control curves. A curve resembling the O2 Monitor curve shown in Figure 6-1.1 should result. The O2 Monitor curve is now complete. LMV5 QSG Rev 4 Sec 6 Pg 5 www.scccombustion.com...
Page 180
OptgMode. Typically, this is set to Con Auto Deact, but other settings are possible. Section 4-2 explains the different choices for this parameter. Note: If necessary, see section 5 for additional troubleshooting information. LMV5 QSG Rev 4 Sec 6 Pg 6 www.scccombustion.com...
Page 181
Also, the PLL52 must be installed within 25 feet of the QGO20. Figure 6-3.1 shows a cut-away of the QGO20 sensor. Figure 6-3.1 Cut-away view of the QGO20 sensor LMV5 QSG Rev 4 Sec 6 Pg 7 www.scccombustion.com...
Page 185
In contrast to no-slip synchronous motors, AC induction motors have slip, so they are only semi-synchronous. Furthermore, the amount of slip depends upon how heavily the motor is loaded. Slip will increase as the motor’s load increases. LMV5 QSG Rev 4 Sec 7 Pg 1 www.scccombustion.com...
Page 186
Setting ramp rates will be discussed later in this section. LMV5 QSG Rev 4 Sec 7 Pg 2 www.scccombustion.com...
Page 187
LMV5 regards an air or fuel actuator. With an air or fuel actuator, the LMV5 sends the actuator a command over the CANBus to move to a certain position. The actuator then rotates, and this change is verified and fine tuned with the feedback potentiometer that is mounted on the actuator’s shaft.
Page 188
6000 4000 2000 Time (sec) Note: The standardization time of 70 seconds was used as an example, but it may be longer or shorter depending upon VSD / LMV5 ramp rates. LMV5 QSG Rev 4 Sec 7 Pg 4 www.scccombustion.com...
Page 190
Fan speed not reached results in an immediate lockout, and Control range limitation VSD Module will result in a lockout if the blower RPM does not come into range in about 5 seconds after the warning is displayed. LMV5 QSG Rev 4 Sec 7 Pg 6...
Page 191
30 Hz output etc… The LMV52 VSD control already contains an application-tuned PID loop, and “stacked” PID loops do not provide accurate control. In short, the VFD needs to be programmed as a slave device. LMV5 QSG Rev 4 Sec 7 Pg 7 www.scccombustion.com...
Page 192
The LMV52 VSD control set-up is now complete, and the blower speed can be set: at each special position, and at each fuel air ratio control point. (Combustion curve) LMV5 QSG Rev 4 Sec 7 Pg 8 www.scccombustion.com...
Page 195
The low-byte of the checksum is transmitted first. Data query: Reading 2 words from address 6 (CRC16 = 0x24A0) Example CRC16 Reply: (CRC16 = 0x0561) Word 1 Word 2 CRC16 LMV5 QSG Rev 4 Sec 8 Pg 1 www.scccombustion.com...
Page 196
Marking for data query or end of reply with data format 10 / 9 bits Example Waiting time = 3.5 characters * 1000 * x bits / Baud rate Baud rate [Baud] Data format [bit] Waiting time [ms] 9600 3.125 2.813 LMV5 QSG Rev 4 Sec 8 Pg 2 www.scccombustion.com...
Page 197
Number of messages The number of addresses per message are limited: 20 addresses of the size of one word when reading 6 addresses of the size of one word when writing LMV5 QSG Rev 4 Sec 8 Pg 3 www.scccombustion.com...
Page 198
Reply time of AZL... to a message from the master 1. Reading data from the LMV5... system: 1...3 addresses 25...75 ms 4...9 addresses 75...125 ms 10...15 addresses 125...175 ms 16...20 addresses 175...225 ms Note These periods of time are defined from the complete writing of the message from the mas- ter to sending the first byte by the AZL...
Page 199
Supply air temperature, in degrees Celsius / -100…+923 °C Slow Fahrenheit (LMV52...) -148..+1693 °F 03/04 Flue gas temperature, in degrees Celsius / -100...+923 °C Slow Fahrenheit (LMV52...) -148...+1693 °F 03/04 Combustion efficiency (LMV52...) PT_Prozent01 0...200 % Slow LMV5 QSG Rev 4 Sec 8 Pg 5 www.scccombustion.com...
Page 200
R 03/04 Selection of manual or automatic operation 0=automatic 0…2 Fast 1=burner on 2=burner off R 03/04 Modbus mode: Local / Remote 0 = Local 0…1 Slow W 06/16 1 = Remote LMV5 QSG Rev 4 Sec 8 Pg 6 www.scccombustion.com...
Page 201
03/04 Startup counter total (read only) 0...999999 Slow 03/04 Fuel volume gas (read only) R/W* See ”Data Slow (resettable from AZL5... version V4.10) types” on 0…199999999.9 m³ page 15 0…1999999999 ft³ LMV5 QSG Rev 4 Sec 8 Pg 7 www.scccombustion.com...
Page 202
Permissible values: 40 %, 50 %, 60 %, 70 %, 80 %, 90 %, 100 % R 03/04 P-value R/W* PT_Prozent01 2...500 % Slow W 16 R 03/04 I-value R/W* Seconds 0...2000 s Slow W 16 LMV5 QSG Rev 4 Sec 8 Pg 8 www.scccombustion.com...
Page 203
Time of day: Hours Time of day: Minutes Time of day: Seconds Startup counter total Hours run total Error history Error code Error diagnostics Error class Error phase Fuel Dummy Output Startup counter total LMV5 QSG Rev 4 Sec 8 Pg 9 www.scccombustion.com...
Page 204
7: Error during identification (path) 8: Error during identification (internally) 9: Monitoring time running 10: Changeover from modulating to multistage during an identification 11: Timeout monitoring time 12: Timeout heating output on path with monitoring LMV5 QSG Rev 4 Sec 8 Pg 10 www.scccombustion.com...
Page 205
The routine used for identifying the path in the integrated load controller (termed “adaption“ here) of the LMV5... system can be controlled and monitored via Modbus. In principle, the general conditions are the same as those used when making adaptions with the AZL52...
Page 206
This setting defines whether the AZL… shall work in Local or Remote mode. Remote mode Display of «Remote Auto», «Remote On», «Remote Off» mode. A change can only be made via Modbus. LMV5 QSG Rev 4 Sec 8 Pg 12 www.scccombustion.com...
Page 207
The maximum permissible data line length between COM2 and a converter is 3 m. In ex- ceptional cases, this data line length can be exceeded, depending on environmental condi- tions (electrical interference) and the type of cable used – without Siemens assuming re- sponsibility.
Page 208
The technical specification provided by the suppliers of the converters must be observed when doing planning work. Some of them do not meet the specifications of the LMV5... system (e.g. operating temperatures). If required, technical measures must be taken (e.g.
Page 210
Operating mode with load controller EEPROM See Basic Documentation «Menu and parameter lists» An AZL5 reset will be triggered when switching power on, or in the event of severe system errors. Note: LMV5 QSG Rev 4 Sec 8 Pg 16 www.scccombustion.com...
Page 213
4) The ability to view and save trends (particularly useful for tuning PID loops) 5) A “dashboard” to view all of the LMV5 inputs and outputs as well as the operating state. The pages following the installation and set-up procedure will explain how to execute these additional functions that the ACS450 offers.
Page 214
9) After the connection at the user level is successful, disconnect from the AZL5 and then reconnect at the service or OEM level, if desired. Remember that a password will be necessary to access the LMV5 on a service or OEM level, and that the password is case sensitive.
Page 215
.mdb file can be viewed or printed with the ACS450 software. Viewing and printing the .mdb file contents 6) Ensure that the ACS 450 software is open, and not connected to the LMV5. Go to the File dropdown menu, and select Show Parameters. When this is selected a window will appear.
Page 216
LMV5, ACS450 will not permit the .par file to be uploaded to the LMV5. The exception to this is if the burner ID on the LMV5 is blank. If the burner ID is blank, then the upload is permitted. If the burner ID is different, two options are available. The next two steps (11 and 12) detail these options.
Page 217
11) Change the burner ID on the LMV5 to match the burner ID contained in the .par file. This can be done via the ACS450 or though the AZL5 directly. The OEM password is required to do this with either method.
Page 218
3) Locate the correct .bin file. The ACS450 will prompt for the file later in this procedure. The .bin file that is necessary for the update is shown below. Contact Siemens to obtain the .bin file if the correct file is not available on the PC.
Page 219
Type a appropriate name in front of the .tbd extension. Thus a valid name would look like : siemens.tdb Notice that the * is no longer in the name. 2) After the name is typed in, click on Open. Also click on Yes when the window appears asking if you would like to create the file.
Page 220
When connected to the AZL5, the ACS450 can provide an overview screen or “Dashboard”. This provides an useful summary of the LMV5 inputs and outputs, as well as the operating state of the LMV5. The following steps outline the procedure for viewing the ACS450 “Dashboard”.
Page 223
Section 10-1 Component Specifications LMV5 Base Unit (120volt) Category Description Units Value Mains Voltage (max) Volts AC Mains Voltage (min) Volts AC Power Mains Frequency (min) Requirements 63.6 Mains Frequency (max) Typ. Power Consumption Watts Fuse FU1 Rating 5 x 20 mm 250 volt Slow-Blow...
Page 224
% R.H. Enclosure IP54 IP rating (first number objects, second water) Mounting All Orientations Notes : Ingress of water and ice are not permitted. For CANBus wiring, use specified cable only. LMV5 QSG Rev 4 Sec 10 Pg 2 ww.scccombustion.com...
Page 225
Ambient Temperature (min) Environmental Ambient Temperature (max) Maximum humidity % R.H. Enclosure IP65 IP rating (first number objects, second water) Mounting All Orientations Notes : Ingress of water and ice are not permitted. LMV5 QSG Rev 4 Sec 10 Pg 3 ww.scccombustion.com...
Page 226
Gasket material Viton Process Size of process connection 1/4" NPT Conn. Ambient Temperature (max) Environmental Ambient Temperature (min) Maximum humidity % R.H. Enclosure IP65 IP rating (first number objects, second water) LMV5 QSG Rev 4 Sec 10 Pg 4 ww.scccombustion.com...
Page 227
IP rating (first number objects, second water) Copper Wire gauge for up to a 300 ft loop (150 ft segment) Wire Gauge Copper Wire gauge for up to a 100 ft loop (50 ft segment) LMV5 QSG Rev 4 Sec 10 Pg 5 ww.scccombustion.com...
Page 228
Copper Wire gauge for up to a 300 ft loop (150 ft segment) Wire Gauge Copper Wire gauge for up to a 100 ft loop (50 ft segment) Ambient Temperature (max) Environmental Ambient Temperature (min) Maximum humidity % R.H. LMV5 QSG Rev 4 Sec 10 Pg 6 ww.scccombustion.com...
Page 229
Fuel oil or Natural Gas Ambient Temperature (min) Environmental Maximum humidity % R.H. Enclosure IP40 IP rating (first number objects, second water) Notes : Ingress of water and ice are not permitted. LMV5 QSG Rev 4 Sec 10 Pg 7 ww.scccombustion.com...
Page 230
% R.H. Enclosure IP20 IP rating (first number objects, second water) Mounting All Orientations Notes : Ingress of water and ice are not permitted. For CANBus wiring, use specified cable only. LMV5 QSG Rev 4 Sec 10 Pg 8 ww.scccombustion.com...