Rexroth IndraDrive
F8057 Device overload shutdown
Cause
Power demanded by drives is too high
Power demanded by drives is too high
F8060 Overcurrent in power section
Cause
Short circuit in motor or motor cable
Power section of drive controller is defective
Current loop parameterized differently
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Supply Unit:
The device was switched off due to overload.
Remedy
Use drives with lower peak current
Reduce allowed acceleration of axis or reduce final
velocity to which acceleration takes place
F8057 - Attributes
Display:
F8057
Mess. no.:
F8057 (hex)
Supported by Firmware Variant:
The current in the power transistors has exceeded the maximum allowed
device peak current (cf. S-0-0110, Amplifier peak current).
Note:
In the case of an internal signal voltage error in the power
section, this error message is directly generated when the
device is switched on, before power was demanded from the
power section.
Remedy
Check motor cable and motor for short circuit
Replace drive controller
Check current loop parameterization (cf. motor data
sheet) and correct it if necessary after having contacted
our service department
F8060 - Attributes
Display:
F8060
Mess. no.:
F8060 (hex)
Error Messages
HMV01
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
7-15