DVVK-4FV DIRECT VENT TERMINATION KIT (cont.)
17. To attach the vent connections at the fireplace, be sure the 7"
diameter adapter collar has been installed per step 3. Apply a
bead of silicone sealant to the 4" diameter flex connector, then
slide the flex pipe adapter collar into the fireplace flue collar
and secure by installing a minimum of two screws through the
flue collar and into the adapter. See Figure 52.
18. Apply sealant to the 7" diameter adapter collar, slide outer
flex vent over the collar, then secure with a 7" diameter band
clamp. See Figure 52.
19. Once the lower connections are made and the flex pipe is
secured with support bands as required (3 feet minimum be-
tween supports) then the roof flashing can be installed. See
Figure 53.
Page 34
Figure 52
20. Install the roof flashing, and seal using common constructions
practices.
21. An additional storm collar band is provided in kit that may be
used as an attic insulation shield. The collar can be installed
around the flex pipe (or hard pipe) just above the firestop
thimble. This collar will act as a shield to prevent blown insu-
lation from entering the thimble.
22. To complete the vent installation, install the vent termination
cap to the top of the hard vent pipe assembly. Mate up the
flue and outer telescopes with the hard pipe assembly, then
secure by installing a minimum of two sheet metal screws into
the overlapped flanges of the cap and pipe.
23. Figure 54 shows a completed installation with components
identified and other installation information such as heights
and clearance to combustibles.
Figure 53
31453-6-0914