Mitsubishi Electric PUHZ-W50VHA-BS Service Manual page 68

Air to water heat pump
Hide thumbs Also See for PUHZ-W50VHA-BS:
Table of Contents

Advertisement

Outdoor power circuit board
PUHZ-HW112YHA(-BS)
PUHZ-HW112YHA2(-BS)
PUHZ-HW112YHA2R1(-BS)
PUHZ-HW112YHA2R3(-BS)
PUHZ-HW140YHA(-BS)
PUHZ-HW140YHA2(-BS)
PUHZ-HW140YHA2R1(-BS)
PUHZ-HW140YHA2R3(-BS)
CN5
CN4
Detection of
Connect to the
primary current
outdoor controller
(Connect to the
circuit board
outdoor noise filter
(CN4)
circuit board (CNCT))
TAB connecter
on X52A
Connect to the
RS resistor
TB-P2
Connect to the smoothing
capacitor CB1
OCH439H
Brief Check of POWER MODULE
W Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.).
If they are short-circuited, it means that they are broken.
1. Check of POWER MODULE
1.Check of DIODE circuit
L1 - P1 , L2 - P1 , L3 - P1 , L1 - N1 , L2 - N1 , L3 - N1
2.Check of IGBT circuit
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
Note: The marks, L1 , L2 , L3 , N1 , N2 , P1 , P2 , U , V and W
shown in the diagram are not actually printed on the board.
CN7
Connect to the
outdoor converter
circuit board
(CN7)
P1
P2
+
CN2
Connect to the outdoor controller circuit
board (CN2)
1-5: Power circuit board
signal to the controller board (0-5 V DC)
2-5: Zero cross signal (0-5 V DC)
3-4: Not used [ 5 :
6-5: 16V DC
7-5: 16V DC
W
V
U
L3
L2
L1
N1
N2
TB-C1
Connect to the
smoothing capacitor
+
CB1
, CB2
68
Transmitting
+
1, 2, 6, 7 :
]
TB-U, TB-V,
TB-W
Connect to the
compressor (MC)
Voltage among
phases:
10 V-400 V AC
TB-L1, TB-L2, TB-L3
Connect to the
outdoor converter
circuit board
(L1-OU, L2-OU,
L3-OU)
400 V AC
TB-N1
Connect to the
smoothing capacitor
CB2
and the CK
capacitor
POWER
MODULE