Gas Connections; Gas Connections Connecting Gas Supply Piping - Lochinvar Knight XL 601 Installation & Operation Manual

Outdoor knight xl
Hide thumbs Also See for Knight XL 601:
Table of Contents

Advertisement

4

Gas connections

Connecting gas supply piping
1. Remove the top access panel and refer to FIG.'s 4-1 thru
4-3 to pipe gas to the boiler.
a.
Install ground joint union for servicing, when
required.
b.
Install a manual shutoff valve in the gas supply
piping outside boiler jacket when required by local
codes or utility requirements.
2. Install sediment trap / drip leg.
Figure 4-1 Gas Supply Piping - Model 400
Figure 4-2 Gas Supply Piping - Model 501
24
Outdoor Knight XL Installation & Operation Manual
Figure 4-3 Gas Supply Piping - Models 601 - 801
3. Support piping with hangers, not by the boiler or its
accessories.
The gas valve and blower will not support
WARNING
the weight of the piping. Do not attempt
to support the weight of the piping with
the boiler or its accessories. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.
4. Purge all air from the gas supply piping.
5. Before placing the boiler in operation, check the boiler
and its gas connection for leaks.
a.
The appliance must be disconnected from the gas
supply piping system during any pressure testing of
that system at a test pressure in excess of 1/2 PSIG
(3.5 kPa).
b. The appliance must be isolated from the gas supply
piping system by closing a manual shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 PSIG
(3.5 kPa).
c.
The appliance and its gas connection must be leak
tested before placing it in operation.
Do not check for gas leaks with an open
WARNING
fl ame – use the bubble test. Failure to
use the bubble test or check for gas leaks
can cause severe personal injury, death, or
substantial property damage.
6. Use pipe sealing compound compatible with propane
gases. Apply sparingly only to male threads of the pipe
joints so that pipe dope does not block gas fl ow.

Advertisement