7-2. Description of Operation Circuit

(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the
power supply is cut off.)
(2) When pressing [
] button on the
remote control, receiving beep sounds from the
indoor unit, and the next operation is performed
together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation
can be effected thereafter simply by pressing
[
] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When
[FAN] button is set to LOW, LOW
HIGH, the motor operates with a constant air flow.
°C
+3
+2.5
+2
+1.5
+1
+0.5
Preset
0
temp.
(Preset temp.: 24°C)
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L–.
(2) The Hi POWER, ECO and COMFORT SLEEP
operation cannot be set.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
7-2-2. Cooling operation
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-2-2.
Preset
temp.
+
, MED, MED
+
or
(2) When [FAN] button is set to AUTO, the indoor fan
M+
motor operates as shown in Fig. 7-2-3. When
*1
[FAN] button is set to LOW, LOW
HIGH, the motor operates with a constant air flow.
*1
*1
Preset
temp.
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L–.
– 23 –
FILE NO. SVM-06006
([MODE] button on the remote control is set
to the cooling operation.)
°C
0.5
0
Fig. 7-2-2
°C
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
ON
ON
OFF OFF OFF ON
+
, MED, MED
+
or
M+
*1
*1
*1