The DS6000 series requires an Electronic Industries Association (EIA) 310-D
Section 1 19-inch rack cabinet. The distance between EIA rails, from the front to the
rear of the rack, is 69.5 centimeters (27.36 inches) minimum to 76.5 centimeters
(30.12 inches) maximum. This rack conforms to the EIA standard. Where you place
the support rails in the rack depends on where you intend to position the server or
storage enclosure.
v Review the documentation that comes with your rack enclosure for safety and
v To ensure rack stability, load the rack starting at the bottom.
v If you install multiple components in the rack, do not overload the power outlets.
v Always connect the storage server to a properly grounded outlet.
v Always connect the rack power to at least two different power circuits or sources.

Rack mounting template

The rack mounting template identifies the proper locations for mounting the support
rails.
Use the following template to identify the proper locations for inserting M5 screws
when mounting the support rails and the DS6000 series into a rack. The locations
for the top rail pin and the bottom rail pin are highlighted in the template.
46
Introduction and Planning Guide
cabling considerations.
This reduces the chance of a simultaneous loss of both ac power sources.