Gas Manifold Pressure Adjustment - Lochinvar 399 Installation And Service Manual

Hydronic heating boilers and domestic water heaters 399,999 - 2,070,000 btu/hr models
Table of Contents

Advertisement

Check burner performance by cycling the system while you
observe burner response. Burners should ignite promptly.
Flame pattern should be stable, see
Turn system off and allow burners to cool, then cycle burners
again to ensure proper ignition and flame characteristics.
FIG. 30 Measuring Gas Supply Pressure at Combination
Gas Valve
Nominal Iron
Pipe Size,
(Inches)
10
"
3/4
369
1"
697
"
1 1/4
1,400
"
1 1/2
2,150
2"
4,100
2-1/2"
6,460
3"
11,200
4"
23,500
16,100
Maximum capacity of pipe in thousands of BTU's per hour for gas pressures of 14 Inches Water Column (0.5 PSIG) or less and a total system
pressure drop of 0.5 Inch Water Column (Based on NAT GAS, 1025 BTU's per Cubic Foot of Gas and 0.60 Specific Gravity).
, page 56.
Multiple Unit Installations Gas Supply Pipe Sizing
Length of Pipe In Straight Feet
20
30
40
256
205
174
477
384
328
974
789
677
1,500
1,210
1,020
2,820
2,260
1,950
1,720
4,460
3,610
3,100
2,720
7,900
6,400
5,400
4,870
13,100 11,100
10,000
Installation and
Service Manual

Gas Manifold Pressure Adjustment

IMPORTANT:
referenced
chamber by a hose connected from the
vent of the gas valve regulator to the
chamber pressure tap located on the front
inside portion of the jacket. Reference the
drawings in this section for component
and connection points for pressure
measurement.
connecting a manometer or magnehelic
must be followed to obtain actual net
manifold pressure for normal operation. A
manometer or magnehelic gauge legible
in 0.1" increments up to 10 inches w.c. is
required to check and adjust the manifold
pressure. The regulator cover screw on
the gas valve must be in place and tight at
all times for the unit to operate properly.
1. Loosen knurled knob that fastens the control panel access
door and pull out control panel.
2. Turn the power switch located in the lower left corner
behind the control panel access door to the "O" or "OFF"
position.
3. Remove the top front jacket access panels to access the gas
valves.
TABLE - L
50
60
70
80
155
141
128
121
292
267
246
256
595
543
502
472
923
830
769
707
1,560
1,440
1,330
2,460
2,310
2,100 2,000 1,900
4,410
4,000
3,800 3,540 3,300
9,000
8,300
7,690 7,380 6,870
31
The
gas
valves
to
the
fan
pressurized
The
procedure
90
100
125
150
113
106
95
86
210
200
179
164
441
410
369
333
666
636
564
513
1,250 1,180
1,100
974
1,700
1,540 1,400 1,300
3,000
2,720 2,500 2,340
6,150
5,640 5,130 4,720
are
for
175
200
79
74
149
138
308
287
472
441
871
820