6-7. Additional Refrigerant Amount

<Formula for Calculating Additional Refrigerant Amount>
Do not remove the refrigerant even if the additional refrigerant amount becomes minus result as a result of
calculations by the following formula and operate the air conditioner as it is.
Additional refrigerant amount (kg) = Main piping additional refrigerant amount (kg)
A
: Additional refrigerant amount per meter of actual main piping length (kg)
B
: Additional refrigerant amount per meter of actual branch piping length (kg)
L
: Actual length of main piping (m)
a, b : Actual length of branch piping (m)
Outdoor model
RAV-SM or RAV-SP
1102AT-E
Outdoor unit
1. Be certain to wire the additional refrigerant amount, pipe length (actual length), head and other
specification on the nameplate put on the outdoor unit for recording.
2. Seal the correct amount of additional refrigerant in the system.
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
+ Branch piping additional refrigerant amount (kg)
= A × (L – 18) + B × (a + b – 4)
Standard piping length
Main piping
Branch piping
18 m
2 m
Indoor unit B
Branch piping
CAUTION
– 22 –
www.heronhill.co.uk
Additional refrigerant amount per Meter (kg/m)
A
0.040
Indoor unit A
Branch pipe
b
a
Branch piping
L
Main piping
B
0.020
H
Fax: 01823 665807