Confirming the operation of indoor unit

Run the unit in a normal way, and confirm its operation. (Please end the check run
first before confirmation)
Cold air (or warm air) must be discharged from the indoor unit.
The indoor unit operates normally when air direction or air volume adjustment
button is pressed.
Error code is displayed when operating the indoor unit with the remote controller
before check run.
101
EXTERNAL INPUT & OUTPUT
101 11

Fitting cable (optional parts)

The cable (including connector) that connects to the external input & output terminal is
an optional part.
This cable should not be laid parallel to the connection cable or power supply cable.
Doing so could result in erroneous operation.
2
Fix the Binder (accessory (outdoor unit)).
Pass the cable through the as yet unused knockout hole.
(Please protect the cable with the edge of knockout hole to avoid damage.)
Seal the knockout hole that passes the cable with putty, so that there is no gap.
101 21

External input

101 21 11
Wiring of connector
ON/OFF of the "Low noise mode", "External input priority mode", "Peak cut
mode", and "Stop operation mode" functions can be enabled with an external
field device.
When installing connection cable, specified part (optional parts) must be used.
Refer to section 8.2, Table. A: List of setting, for the required function. The
function must be set for the external input to work.
Input
Low noise mode
External input priority mode
Peak cut mode
Stop operation mode
Outdoor unit
control PC board
1
CN931
2
1
CN932
2
1
CN933
2
1
CN934
2
* Make the distance from the PC board to the connected unit within 10m.
• Contact capacity : 24VDC or more, 10mA or more.
9379069366_IM.indb 18
When fitting the service cover,
pull the cable as shown in
the diagram to prevent it from
being trapped.
And fix the 2 binders
(accessory (optional parts)).
cable
3
Connector
CN931
CN932
CN933
CN934
Circuit diagram example
Connected unit
(Field supply)
Ex.) Switch
Connection cable (option)
*10 m
Signal
Connector
101 21 21
Low noise mode (CN921)
• This features reduces the operating sound of the outdoor unit from the
normal sound. The air conditioner is set to the "Low noise mode" when
closing the contact input of a commercial timer or ON/OFF switch to a
connector on the outdoor control PC board.
* Performance may drop depending on the outside air temperature
condition, etc.
* Set the "Low noise mode" level, refer to "8.2. Function settings".
Input Signal ···ON : Low noise mode
···OFF : Normal operation
Input Signal
ON
OFF
Low noise mode
ON
OFF
101 21 21
External input priority mode (CN922)
• It is possible to switch to cooling operation and heating operation by
using external input.
* Set the "External input priority mode", refer to "8.2. Function settings".
Input Signal ···ON : Heating operation
···OFF : Cooling operation
Input Signal
ON
OFF
Priority mode
Heating
Cooling
101 21 41
Peak cut mode (CN933)
• Operation that suppressed the current value can be performed by
means of the connected unit. The air conditioner is set to the Peak cut
mode by applying the contact input of a commercial ON/OFF switch to a
connector on the outdoor control PC board.
* Set the "Peak cut mode" level, refer to "8.2. Function settings".
Input Signal ···ON : Peak cut mode
···OFF : Normal operation
Input Signal
ON
OFF
Peak cut mode
ON
OFF
101 21 21
Stop operation mode (CN924)
• It is possible to switch to Batch stop or Emergency stop and Normal
operation by using external input.
* Set the "Batch stop" or "Emergency stop" pattern, refer to "8.2. Function
settings".
• When function setting is "Batch stop" mode
On
Input signal
Off
Operation
Indoor unit
Stop
Remote controller
• When function setting is "Emergency stop" mode
On
Input signal
Off
Operation
Indoor unit
Stop
Remote controller
On
On
On
On
On
En-18
15/11/2555 11:18:27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents