Fujitsu AS* G09LECB Service Instruction page 20

Split type room air conditioner, wall mountedtype inverter
Table of Contents

Advertisement

3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
O
utside temp. > -10°C
Tn -Tn10<-5deg
Tn < - 17°C
=
Tn -Tnb <-2deg
However,Tn< 6°C
=
Heating operation start : Compressor ON
Normal defrost
Outside temp.< -20°C
=
-20
°C< Outside temp.< -10°C
=
Tn <
=
Outside temp.- 7°C
or
Tn < - 20°C
=
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Outdoor HEX temp.: Over 16°C
Compressor ON time: Maximum 15 minutes
(Not defrosted for 10 minutes)
Intermittent operation
Compressor
OFF count :
Tn <
40 times
=
Outside temp.- 7°C
(Less than 10min.)
or
Tn < - 30°C
=
Defrost start
Outdoor fan : OFF
Compressor speed : 0 rps
EEV : 480pulse
4-way valve : OFF
Compressor speed : 90rps
or
Defrost end
01-17
Integrating defrost
Continuous operation
Compressor
Compressor
integrating
integrating
operation:
operation:
Over 240 min.
Over 213 min.
Outdoor
Outdoor
heat exchanger
heat exchanger
temperature:
temperature:
Below - 3°C
Below - 5°C