Pressure On Service Port - Heat Controller B-DVH09SD-0 Service Manual

Inverter single zone ductless mini-split
Table of Contents

Advertisement

Heat Controller

10.4: Pressure on Service Port

10.4.1 Cooling:
(℃)
BAR
BAR
BAR
(℃)
PSI
PSI
PSI
(℃)
MPA
MPA
MPA
12.0
10.0
8.0
6.0
4.0
2.0
0.0
IDT
75
ODT
(23.89)
70/59
8.2
75/63
8.6
80/67
9.3
IDT
75
ODT
(23.89)
70/59
119
75/63
124
80/67
135
IDT
75
ODT
(23.89)
70/59
0.82
75/63
0.86
80/67
0.93
75 (23.89) 85 (29.44)
85
95
(29.44)
(35)
7.8
8.1
8.3
8.7
8.9
9.1
85
95
(29.44)
(35)
113
117
120
126
129
132
85
95
(29.44)
(35)
0.78
0.81
0.83
0.87
0.89
0.91
95 (35)
105 (40.56) 115 (46.11)
49
DVC/DVH Inverter Mini-Split
105
115
(40.56)
(46.11)
8.6
10.1
9.1
10.7
9.6
11.2
105
115
(40.56)
(46.11)
125
147
132
155
140
162
105
115
(40.56)
(46.11)
0.86
1.01
0.91
1.07
0.96
1.12
70/59
75/63
80/67