Turbo Air TAS-09EH/O Service Manual page 47

Dc inverter split air-condition unit
Hide thumbs Also See for TAS-09EH/O:

Advertisement

Fig. 3 the indoor and outdoor connecting
cable's technics after 2007
The voltage stabilizing diode
ZD1 、ZD2 reference value:
Forward
resisitance
reverse resistance:∞
The limited current resistance
value:14.8 kΩ
Note:there are two kinds of connecting technics for the indoor and
outdoor connecting cable, Fig 2 shoed the technics before 2007, and
Fig 3 showed the technics after 2007
:713 Ω
47
Fig. 2 the indoor and outdoor connecting
cable's technics before 2007
PTC1 resistance value:
1.02KΩ(25℃)
The voltage of the cross flow
fan feedback end will be
increased gradually from 0 to
+2.4VDC when turning on
the indoor unit