Fujitsu AB*14LBAJ Service Instruction page 94

Split type room air conditioner universal floor / ceiling / duct / cassette wall mounted / floor type inverter multi
Hide thumbs Also See for AB*14LBAJ:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 6
Outdoor Unit Fan Motor
Check Point : AO*18LMAK2/ 24LMAM2
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
150°C
BLUE
RED
Pr
BLACK
WHITE
Read Wire
White - Red
Red - Black
(AC)
Red - Blue
02-56
Resistance value
54.7
8%
96.3
8%
185
8%
at 20°C

Hide quick links: