Contents Model Number Nomenc lature ....................2 General Data ..........................3 Dimensions ..........................5 Wiring Dia gram ........................6 Troub leshooting Guide ......................7 Features of Contr oller ......................18 Exploded View and Replacement Parts List ..............23 Model Number Nomenc lature C 0 9 0 B T 0 0 Development Sequence Model Type A(0): Gold Fin...
General Data List of Functions Features Model No. TN-C090BT00 TN-C120BT00 Cooling & Fan Operation Auto Restart Operation Wired Remote Control Group Control Child Lock Function Self Diagnosis Function Weekly Program Time Delay Relay Two Thermistor Control Central Control Zone Control...
Page 4
General Data Model No. TN-C180BT00 TN-C240BT00 Features Cooling & Fan Operation Wired Remote Control d l i Time Delay safety Two Thermistor Control Central Control Zone Control Energy Saving Gold Fin Option Option Electric Heater Fire Alarm Function Electronic Thermostat c t i High Pressure Switch Phase Protection...
Troubleshooting Guide In general, possible trouble is classified in two causes. The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application. Unit runs but ineffective cooling Ineffective Cooling Check of cold air cir-...
Page 14
Troubleshooting Guide Fails to Start Check power source. Check of circuit breaker and fuse. Check control switch Check control switch. setting. Compressor only fails to Fan only fails to start. start. Improper wiring. Drop of power voltage. Loose terminal connection. Defect of fan motor Improper wiring capacitor.
Page 15
Troubleshooting Guide VOLTAGE LIMITS NAME PLATE RATING MINIMUM MAXIMUM 380 - 415 V 342 V 456 V 1. No cooling and heating operation performed 1) Both the blower and the compressor do not work WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Other parts except the Electric supply interrupted...
Page 16
Troubleshooting Guide 3) Only outdoor fan does not work WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Motor Over-heated Check how it is insulated. Repair or replace it. Wire short Electric Wiring Cut off of wiring Check it with a tester. Rewiring or repair.
Troubleshooting Guide 2. The Units discontinue after the operation started WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Wash it by means of Coil is dirty *1 Checking Outdoor coil something like chemical washing. Extract air by vacuum Air intruded into the In the event that In-condensable gas pump, then replenish...
Troubleshooting Guide 3. The unit is working, but not cooling and heating sufficiently (Both blower and compressor are working) WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Load Much Cooling or Heating Heat load increased. Do necessary disposal Window or door has many load respectively.
Electronic parts Troubleshooting Guide Possible trouble 1 : The unit does not operate. 1. Check the Fuse. Is the input voltage of 2. Check the wiring of AC220V. transformer AC220V? Is the output voltage of 1. Exchange the transformer. transformer AC24V & AC13V? 2.
Page 20
Electronic parts Troubleshooting Guide Possible trouble 3 : Key input of remote-controller does not respond. 1. Check or repair Connector wiring. Is the connection between MAIN PCB and remote-controller 2. Exchange the Connector. correct? 1. Replace the pressed key. Is any key on the remote-controller 2.
Page 21
Electronic parts Troubleshooting Guide Possible trouble 5 : No cooling operation performed. Is the unit operating? 1. Press power ON/OFF button. 1. Press cooling operation key. Is the cooling mode? 2. After reenergizing power supply, press power "ON/OFF" button. 1. Set flowing. Set Temp.
Page 22
Electronic parts Troubleshooting Guide Possible trouble 7 : No humidifier operation performed. 1. Press cooling or fan operation Is the indoor fan operation? or heater operation key. Is the HUMID LCD "ON"? 1. Press humidifier Key. Is the output 1. Check or exchange IC02D voltage of Micom's 3PIN on on the MAIN PCB.
Page 23
Electronic parts Troubleshooting Guide Possible trouble 8 : Indoor motor does not operate. 1. Press power ON/OFF button. Is the unit operating? 2. Reconnect the power supply. Is the output voltage of Micom's 10PIN on 1. Check or exchange IC01D, the MAIN PCB 5V? IC02D on the main PCB.
Page 27
3. Feature of Remote-Controller PCB ASS'Y 4. Feature of Remote-Controller LCD...
Page 28
5. Error Mode & Corrective Method Cause of error Sensing condition of error Method of SVC Error mode Remark OPEN/SHORT of Room Voltage of sensing: Over 4.8V 1. Check the voltage of "CO1H" temp.(25 C) on the remote controller. CH01 room temp.
Page 29
9. Explanation of principal function Flow Chart START(Power supply) 1. Initialize "micom". 2. A/D convert. 3. Main PCB: Waiting cooling operation. 4. Remote controller: Waiting input. Dehumidification Mode? Power ON? Dehumidification operating Cooling Mode? Stop condition? Go to A Set Temp. < Indoor Temp. Time delay mode Cooling operating Stop condition?