Refrigerant Charge - International comfort products N4H3 Installation Instructions Manual

R?410a split system heat pump
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS

REFRIGERANT CHARGE

A. COOLING MODE
Outdoor units are shipped with a refrigerant charge to
match a specific
indoor coil and 15 feet (4.6m) of
refrigerant line. If shorter or longer refrigerant lines or a
different indoor coil are used, the charge will have to be
adjusted.
For different line lengths, add or remove charge based on
0.6 ounces (17g) charge per foot (305mm) of difference.
For example, a 25 foot (7.6m) line set is 10 feet (3m)
longer than the specified 15 feet (4.6m). Add 0.6 ounces
(17g) charge for each of the extra 10 feet (3m):
10 x 0.6 = 6.0 ounces additional charge
(3m x 17g = 51g additional charge)
This outdoor unit is designed for use only with indoor coils
that utilize a TXV refrigerant metering device. With an
indoor TXV, use the subcooling method to make final
charge adjustments:
NOTE: Only use subcooling charging method when
S outdoor ambient temperature is between 70_F and 100_F
(21_C and 38_C)
S indoor temperature is between 70_ and 80_F (21_C and
27_C)
S line set is less that 80 feet (24.4m).
1. Operate unit a minimum of 15 minutes before
checking charge.
NOTE: If outdoor unit has a 2−speed fan motor,
motor will operate in low speed when outdoor
ambient temperature is below 82° F (28° C). Pull
one of the yellow low voltage wires off the fan
control and the unit will default to high speed fan for
servicing. Reconnect wire after servicing.
2. Measure liquid service valve pressure by attaching
an accurate gauge to service port.
12
R−410A Split System Heat Pump
3. Measure liquid line temperature by attaching an
accurate thermistor type sensor or electronic
thermometer to liquid line near outdoor coil.
4. Refer to unit rating plate for required subcooling
temperature.
5. Refer to Figure 13. Find the required liquid line
temperature where the rating plate subcooling
temperature intersects measured liquid service
valve pressure.
6. If the measured liquid line temperature is higher
than the chart number, add refrigerant to lower the
measured temperature.
NOTE: When adding refrigerant, charge in liquid
form, using a flow restricting device, into the
suction port.
If the measured liquid line temperature is lower
than the chart number, reclaim refrigerant to raise
the measured temperature.
Tolerance is | 3° F (|1.7_C).
B. HEATING MODE
To check system operation during heating cycle, refer to
the Tech Label on outdoor unit. This chart indicates
whether a correct relationship exists between system
operating pressure and air temperature entering indoor
and outdoor units. If pressure and temperature do not
match on chart, system refrigerant charge may not be
correct. Do not use chart to adjust refrigerant charge.
NOTE: When charging is necessary during heating
season, charge must be weighed in accordance with unit
rating plate ±0.6 ounces per foot of a inch liquid line
above or below 15 feet respectively (±17g per 305mm of
10mm liquid line above or below 4.6m respectively).
428 01 5102 00

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

C4h3H4h3T4h3N4h4C4h4H4h4 ... Show all

Table of Contents