STEP 4: INSTALLING & TESTING GAS PIPING
PROCEDURE A: Select gas pipe size which will result in a pressure drop of less than 0.3" W.C. for natural
gas or 0.5" W.C. for propane, following example below.
Example: Boiler Model HC-120D is to be installed. Distance from existing gas meter to installation site is 20 ft.
What pipe size must be used? Local utility indicates heating value of natural gas being supplied is 1020 Btu per
cu.ft. Determine cubic feet of gas per hour for above boiler model:
120,000 Btu per hour
1020 Btu per cu.ft.
1. Find 20 ft. in upper portion of the table for natural gas under "Length of Pipe, Feet" heading.
2. Moving down the column, match required capacity. Higher capacity acceptable. In our case it is 190 cu.ft.
3. Move to left-hand column "Nominal Iron Pipe Size, Inches"; read required pipe size. In our case it is 3/4".
Maximum Capacity of Pipe in Cubic Feet of Natural Gas per Hour for Gas Pressures of
Nominal
Iron Pipe
Internal
S i z e ,
Diameter
10
1 0
I n c h e s
I n c h e s
1/4"
32
.326
3/8"
72
.493
1/2"
132
.622
3/4"
278
.824
1"
520
1.049
1-1/4"
1,050
1.380
1-1/2"
1,600
1.610
2"
3,050
2.067
2-1/2"
4,800
2.469
3"
8,500
3.026
4"
17,500
4.026
Maximum Capacity of Pipe in Thousands of Btu per Hour of Undiluted Liquefied
Maximum Capacity of Pipe in Thousands of Btu per Hour of Undiluted Liquifi
Petroleum gases (at 11 Inches of Water Column Inlet Pressure)
Nominal
Iron Pipe
S i z e ,
I n c h e s
1/2"
3/4"
1"
1071
1-1/4"
2205
1-1/2"
3307
2"
6221
= 117.6 cu.ft. per hour
0.5 Psig or Less and a Pressure Drop of 0.3 Inch Water Column
(Based on a 0.60 Specific Gravity Gas)
20
30
40
50
2 0
3 0
4 0
5 0
22
18
15
49
40
34
92
73
63
190
152
130
115
350
285
245
215
730
590
500
440
1,100
890
760
670
2,100
1,650
1,450
1,270
3,300
2,700
2,300
2,000
5,900
4,700
4,100
3,600
12,000
9,700
8,300
7,400
Petroleum Gases (at 11 Inches Water Colum Inlet Pressure)
(Based on aPressure Drop of 0.5 Inch Water Column)
(Based of a Pressure Drop of 0.5 Inch Water Column)
10
20
30
40
1 0
2 0
3 0
4 0
275
189
152
129
567
393
315
267
732
590
504
1496
1212
1039
2299
1858
1559
4331
3465
2992
Length of Pipe, Feet
60
70
80
6 0
7 0
8 0
14
12
11
11
30
27
25
23
56
50
46
43
105
96
90
195
180
170
400
370
350
600
560
530
1,150
1,500
990
1,850
1,700
1,600
1,500
3,250
3,000
2,800
2,600
6,800
6,200
5,800
5,400
Length of Pipe, Feet
50
60
70
80
5 0
6 0
7 0
8 0
114
103
96
89
237
217
196
185
448
409
378
346
937
834
771
724
1417
1275
1180
1086
2646
2394
2205
2047
9
90 100 125
150
9 0
1 0 0
1 2 5
1 5 0
10
9
8
8
22
21
18
17
34
40
38
31
84
79
72
64
160
150
130
120
320
305
275
250
490
460
410
380
930
870
780
710
1,400
1,250
1,130
2,500
2,200
2,000
4,500
5,100
4,100
90 100 125
9 0
1 0 0
1 2 5
150
1 5 0
83
78
69
63
173
162
146
132
275
322
307
252
677
630
567
511
1023
967
866
787
1921
1811
1606
1498
175
200
1 7 5
2 0 0
7
6
15
14
28
26
59
55
110
100
225
210
350
320
650
610
1,050
980
1,850
1,700
3,800
3,500
FIGURE 1.16