Earth Leakage Circuit Breaker For Heater; Relay For Heater; Booster Heater; 2 + 4Kw Heater (230V, 1 Phase) - Mitsubishi Electric EHSD-MEC.UK Service Manual

R410a hydrobox
Hide thumbs Also See for EHSD-MEC.UK:
Table of Contents

Advertisement

Part Name

Earth leakage circuit breaker for heater

Relay for heater

R
S
T
U
V
W

Booster heater

Thermostat (90 °C) and thermal cut out (121 °C)
121 °C
Thermal
cut-out
9
10
2kW heater (230V, 1 phase)
2kW
1

2 + 4kW heater (230V, 1 phase)

2kW
1
2
3 + 6kW heater (400V, 3 phase)
1kW
1kW
1kW
1
2
3
3 + 6kW heater (230V, 3 phase)
1kW
1kW
1kW
1
2
3
4
OCH571
A1 A2
90 °C
Manual reset
water
thermostat
2
2kW
2kW
3
4
2kW
2kW
2kW
4
5
6
2kW
2kW
2kW
5
6
If a short circuit occurs on the booster heater, immersion heater, or each power line, a
short-circuit breaker will trip and power source will be blocked.
Eliminate the causes of short circuit and then turn on the breaker again.
When the applied voltage is not 230V AC across the terminals A1-A2, check the terminals
R-U, S-V, and T-W are open.
When the applied voltage is 230V AC across the terminals A1-A2, check the terminals
R-U, S-V, and T-W are short.
Measure the resistance between the terminals with a tester.
Terminal
Normal
9-10
110(±35)mΩ
Terminal
Normal
1-2
26.5(+3/-1.3)Ω
Terminal
Normal
1-2
26.5(+3/-1.3)Ω
3-4
13.3(+1.5/-0.6)Ω
Terminal
Normal
1-2=2-3=1-3
105.8(+11.8/-5)Ω
4-5=5-6=4-6
52.9(+5.8/-2.5)Ω
Terminal
Normal
35.3(+3.9/-1.8)Ω
1-2=2-3=3-1
4-5=5-6=6-4
17.6(+1.9/-0.9)Ω
54
Check Points
Abnormal
Open or Short
Abnormal
Open or Short
Abnormal
Open or Short
Open or Short
Abnormal
Open or Short
Open or Short
Abnormal
Open or Short
Open or Short