Fault Findings - Stanley BRANDON Operation Instructions Manual

80k/100k gas fired cooker
Hide thumbs Also See for BRANDON:
Table of Contents

Advertisement

PROBLEM
1.
Poor Flue Draught:
2.
Excessive Flue Draught
3.
Down Draught:
4.
Cooker Smoking:
5.
Hot Plate Not Heating:
6.
Oven Not Heating:
7.
Radiators Not Heating:
8.
Domestic Hot Water
Cylinder not getting
hot enough:
9.
Intermittent Performance: (a) Cooker starved of primary air.
10. Domestic Hot Water
Rusty:
It is of the utmost importance to keep the flue pipe and chimney clear of deposits. Blocked or partially
obstructed flueways and chimneys may cause dangerous fumes to be emitted into the room, these may well
be invisible.
Manufactured by
Waterford Stanley Ltd.,
Unit401-403, IDA Industrial Estate, Cork Road,
Waterford, Ireland.
Tel: (051) 302300 Fax (051) 302315

FAULT FINDINGS

CAUSE
(a) Obstruction.
(b) Chimney too low.
(c) Chimney too wide.
(d) Crack in wall.
(e) No flue liner
(a) High chimney.
(a) High trees
(b) High buildings
(c) Low chimney.
(d) Negative pressure zone.
(a) Insufficient primary air.
(b) Chimney choked.
(c) Downdraught.
(d) Poor combustion.
(a) Burner cutting out.
(b) Utensils not flat.
(a) Flueways blocked with soot.
(a) Circulating pump not working.
(b) Pipe thermostat set too high.
(c) Air in system.
(d) Pipe system faulty.
(e) Excessive number of radiators
(f) Radiator valves not balanced.
(g) By-pass incorrectly set.
(a) Cylinder too large.
(b) Flow pipe too large.
(c) Check valve' is closed.
(d) Cylinder thermostat set too low.
(e) Circulating pump not working.
(b) Extraction fan in room.
(c) Dirty burner.
(a) Leak in indirect cylinder.
(b) Incorrect cylinder fitted.
REMEDY
(a) Clear and clean.
(b) Raise height above ridge.
(c) Fit flue liner 150mm (6")
(d) Repair cracks.
(e) Fit flue liner
(a) Fit draught stabiliser.
(a) Raise chimney height.
(b) Raise chimney height.
(c) Raise chimney height.
(d) Fit anti-down draught cowl.
(a) Provide additional room air inlet or adjust burner air intake.
(b) Clean chimney.
(c) Raise chimney height or fit anti-downdraught cowl.
(d) Check air supply, adjust settings.
(a) Increase cooker thermostat setting.
(b) Use machined based utensils.
(a) Clean out.
(a) Check and replace if defective.
(b) Reduce thermostat settings.
(c) Bleed system.
(d) Check pipe sizes and circuit.
(e) Turn off un-needed radiators.
(f) Adjust valves to give an even flow.
(g) Adjust by-pass valve
(a) Use 180 litre cylinder.
(b) Use 28mm bore pipe.
(c) Open 'check valve'.
(d) Increase thermostat setting.
(e) Check and replace if defective.
(a) Provide air inlet in room.
(b) Provide additional air inlet in room.
(c) Service burner.
(a) Replace cylinder.
(b) Check with installer.