Configuration

2.5 Operation When Setting Cycle for Logging Trigger

When setting Cycle for logging triggers, the time of the first trigger is adjusted to perform
subsequent logging at good timing.
 When the unit of cycle is second or minute, adjust to occur a tirgger at 0 min. 0 sec. of every
hour.
 When the unit of cycle is time, adjust to occur a trigger at 00:00:00 of every day.
 Example of timing of trigger occurrence (when the unit of cycle is second)
Time at which
logging trigger
condition is met
12:01:05
12:01:05
12:01:05
12:01:05
12:01:05
12:01:05
12:01:05
12:01:05
 Example of timing of trigger occurrence (when the unit of cycle is minute)
Time at which
logging trigger
condition is met
12:01:00
12:03:00
12:05:00
12:05:00
12:05:00
12:01:00
12:59:00
12:10:00
 Example of timing of trigger occurrence (when the unit of cycle is hour)
Time at which
logging trigger
condition is met
12:59:00
12:59:00
12:30:00
12:30:00
12:30:00
12:30:00
12:30:00
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
2-14
Time at which the 1st
Set cycle
trigger occurs after
adjustment
1 second
12:01:06
2 seconds
12:01:06
3 seconds
12:01:06
4 seconds
12:01:08
5 seconds
12:01:10
10 seconds
12:01:10
15 seconds
12:01:15
30 seconds
12:01:30
Time at which the 1st
Set cycle
trigger occurs after
adjustment
1 minute
12:02:00
2 minutes
12:04:00
3 minutes
12:06:00
4 minutes
12:08:00
5 minutes
12:10:00
10 minutes
12:10:00
15 minutes
13:00:00
30 minutes
12:30:00
Time at which the 1st
Set cycle
trigger occurs after
adjustment
1 hour
13:00:00
2 hours
14:00:00
3 hours
15:00:00
4 hours
16:00:00
6 hours
18:00:00
12 hours
24:00:00
24 hours
24:00:00
Time at which subsequent
triggers occur
12:01:07, 12:01:08
12:01:08, 12:01:10
12:01:09, 12:01:12
12:01:12, 12:01:16
12:01:15, 12:01:20
12:01:20, 12:01:30
12:01:30, 12:01:45
12:02:00, 12:02:30
Time at which subsequent
triggers occur
12:03, 12:04, 12:05
12:04, 12:06, 12:08
12:09, 12:12, 12:15
12:12, 12:16, 12:20
12:15, 12:20, 12:25
12:20, 12:30, 12:40
13:15, 13:30, 13:45
13:00, 13:30, 14:00
Time at which subsequent
triggers occur
14, 15, 16 o'colock ...
16, 18, 20 o'colock ...
18, 21, 24 o'clock ...
20, 24, 28 o'clock ...
24, 30, 36 o'colock ...
36, 48, 60 o'clock ...
48, 72, 96 o'clock ...