Disconnect terminal X6YA from X6Y and connect X6YB to X6Y.
L N
30 31
X2M
X6YB
X6YA
X6Y
When the outdoor unit is connected to a benefit kWh rate power
supply, the voltage free contact of the receiver controlling the benefit
kWh rate signal of the electricity company must be connected to
clamps 17 and 18 of X2M (as illustrated in the figure above).
When parameter [D-01]=1 at the moment that the benefit kWh rate
signal is sent by the electricity company, that contact will open and
the unit will go in forced off mode
When parameter [D-01]=2 at the moment that the benefit kWh rate
signal is sent by the electricity company, that contact will close and
the unit will go in forced off mode
Type 1
This type of benefit kWh rate power supply is not interrupted.
Type 2
This type of benefit kWh rate power supply is interrupted after elapse
of time.
Type 3
This type of benefit kWh rate power supply is interrupted immediately.
In case the benefit kWh rate power supply function is
enabled, the screed dry-out function can not be
enabled.
When connecting the equipment to a benefit kWh rate
power supply, change field setting [D-01]. In case the
benefit kWh rate power supply is of the type that
power supply is not interrupted (like illustrated above
as type 1) change both field settings [D-01] and
[D-00]. Refer to
supply/Local shift value weather dependent" on
page 33
of chapter
If the benefit kWh rate power supply is of the type that
power supply is not interrupted, the unit will be forced
to off. Controlling the solar pump is still possible.
When the benefit kWh rate signal is sent, the
centralised control indicator e will flash to indicate
that the benefit kWh rate is active.
(1) When the signal is released again, the voltage free contact will close and
the unit will restart operation. It is therefore important to leave the auto
restart function enabled. Refer to
(2) When the signal is released again, the voltage free contact will open and
the unit will restart operation. It is therefore important to leave the auto
restart function enabled. Refer to
EKHVH/X008BB6V3 + EKHVH/X008BB6+9WN
Daikin Altherma indoor unit
4PW64329-1 – 07.2010
L N
30 31
X2M
X6YA
X6YB
X6Y
(1)
.
(2)
.
"[D] Benefit kWh rate power
"Field
settings".
"[3] Auto restart" on page
28.
"[3] Auto restart" on page
28.

Installation and connection of the remote controller

The unit is equipped with a remote controller offering user-friendly
way to set up, use and maintain the unit. Before operating the remote
controller, follow this installation procedure.
The wiring for connection is not included.
NOTICE
The remote controller, delivered in a kit, has to be mounted
indoors.
1
Remove the front part of the remote controller.
Insert a slotted screwdriver into the slots (1)
in the rear part of the remote controller, and
remove the front part of the remote
controller.
2
Fasten the remote controller on a flat
surface.
Be careful not to distort the shape of the lower part of
the remote controller by over tightening the mounting
screws.
3
Wire the unit.
Wired from the back
X2M
1 1
2
P2
P1
3
4
1
Unit
2
Rear part of the digital controller
3
Front part of the digital controller
4
Wired from the rear
5
Wired from the top
A
When wired from the sides, notch the part for he wiring to
pass through with nippers
Connect the terminals on top of the front part of the remote
controller and the terminals inside the unit (P1 to X2M: 16, P2 to
X2M: 16a).
NOTICE
Peel the shield for the part that has to pass
through the inside of the remote controller
case ( l ).
4
Reattach the upper part of the remote controller.
NOTICE
Be careful not to pinch the wiring when attaching.
First begin fitting from the clips at the
bottom.
1
Wired from the sides
A
X2M
1
A
2
A
A
P2
P1
3
5
Installation manual
1
23