7-2-9. Operating rate output

Header outdoor unit
Operation
At the output terminals, a signal is present (relay closed) or absent (relay open) in various combinations according
to the system operation factor, as shown in the diagram.
The operation rate (FA) is the percentage ratio of the current output of the system to the maximum output (100%).
Function
SW16
System operation
rate output
Bit 1: ON
Bit 2: OFF
off = Relay open
on = Relay closed
C2
Connection cable 2
Interface-side connector (green)
CN514
MONITOR
Monitoring device
OUTPUT1
Output terminal for each function
OUTPUT2
Output terminal for each function
OUTPUT3
Output terminal for each function
PJ20
Connector on optional PCB side
Terminal block
TB1
* Connect the optional P.C. board to the header outdoor unit.
Note 1: Output Relay (K1, K2, K3) Contact Specifications
• Output terminals (OUTPUT1, 2, 3) must satisfy the following electrical rating.
• When connecting a conductive load (e.g. relay coil) to loads K1, K2 and K3, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
<Electrical Rating>
24 V or less (AC / DC), 10 mA or more, 1 A or less (non-conductive load)
Outdoor unit
Optional PCB
interface PCB
OUTPUT1
off
on
off
on
off
on
off
on
Locally procured
Shield
wire
OUTPUT2
OUTPUT3
off
off
off
off
on
off
on
off
off
on
off
on
on
on
on
on
58
(See "NOTE")
MONITOR
Operation factor (FA)
FA=0%
0%
<
FA
<
20%
<
20% FA
35%
<
35% FA
50%
<
50% FA
65%
<
65% FA
80%
80% FA
<
95%
95% FA