Powerful Mode Operation - Panasonic CU-E9DKE Service Manual

Hide thumbs Also See for CU-E9DKE:
Table of Contents

Advertisement

This document is protected (secured) by www.nettovarmepumpar.se
C. Control contents
a. Fan Speed manual
1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
2. Fan speed for quiet operation is -1 step from setting fan speed.
3. Fan Speed Auto
Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.

8.1.11. Powerful Mode Operation

When the powerful mode is selected, the internal setting temperature will shift to achieve the setting temperature quickly.
(a) Cooling Operation
(b) Soft Dry Operation
(c) Heating Operation
8.1.12. Delay ON Timer Control
Delay ON timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is to
provide a comfortable environment when reaching the set ON time.
60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to determine the
indoor intake air temperature and outdoor air temperature in order to judge the operation starting time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
31
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs-e9dkewCs-e12dkewCu-e12dke

Table of Contents