Haier HSU18VHJ(DB) Service Manual page 68

Wall mounted type dc inverter e-series
Hide thumbs Also See for HSU18VHJ(DB):
Table of Contents

Advertisement

A
Check the status of LED1
on the indoor mainboard. If
the LED1 blinks
No
Test the outdoor power supply
(230VAC and +310VDC) with a
multimeter.
If 230VAC is available but
310DC not, the power module is
damaged, replace it with a new
one.
If both 230VAC and 310DC
are
available,
measure
+12V(from7805)is available.
YES
If the LED1 is off within two minutes
after the machine is supplied with
power, measure the AC
between positions 1 and 3 on the
terminal
of
outdoor
unit
multimeter.
If the value varies between 0 and 80
VAC, the outdoor mainboard is
damaged, replace it with a new one.
HSU12/18VHJ(DB)
NO
The outdoor mainboard is
damaged; Replace them with a
new one.
If the value is constant at about 30V,
voltage
the indoor mainboard is damaged,
replace it with a new one.
with
a
The outdoor mainboard is damaged;
replace it with a new one.
65
Yes
measure
the
voltage
Jumpers 3 and 4 of IC8 on the indoor
mainboard with a multimeter.
If the voltage is of a
constant value of 0V
DCto5V DC
Yes
The
indoor
mainboard
damaged; replace it with a new
one.
Domestic Air Conditioner
Functions and control
between
is
NO