5-14 Contacts for Building Automation

5-14.1 INPUT CONTACT (J4 - green)
The status of this input affects system operation according to the following:
Contact OPEN :
Contact CLOSED:
5-14.2 OUTPUT CONTACT (J12)
This connector is directly tied to the contact (normally open) of a power relay which activates every time
the following alarm condition occur:
RAT damaged
ICT damaged
In this case when alarm happens, on poles 1 and 3 of J12 connector, 220 VAC-50Hz are available.
Max electrical load: 1A- 240VAC
system does not operate (always OFF) – inputs from wireless remote controller are not processed
system operates in the normal way according to the inputs coming from wireless remote controller
23