Refer to the below charts for the proper settings for the SU-2A burner and PNA boiler. Note: a
pressure change at the valve, and, in some cases, an orifice change, is all that is required to
convert a natural gas burner to a LPG (propane) unit and vice-versa.
Boiler Model
Burner
DK2-3
SU-2A
DK2-4
SU-2A
DK2-5
SU-2A
DK2-6
SU-2A
DK2-7
SU-2A
DK2-8
SU-2A
BURNER SETTINGS
Chart 3: Heat Wise Burner Settings for
PNA DK-2 Series Boilers (Gas & LPG)
Fuel
Input
Nat. Gas
98,000
Propane
98,000
Nat. Gas
140,000
Propane
140,000
Nat. Gas
175,000
Propane
175,000
Nat. Gas
194,000
Propane
194,000
Nat. Gas
224,000
Propane
224,000
Nat. Gas
250,000
Propane
250,000
Orifice
Head
Air
7/32"
21
0.5
7/32"
20
0.5
1/4"
16
5
1/4"
16
5
19/64"
15
11
19/64"
15
11
21/64"
13
13.25
21/64"
13
13.75
27/64"
11
16
27/64"
11
16.25
none
3
15
none
3
15
7
Manifold
Pressure ("W.C.)
3.5
2.3
3.5
1.8
3.5
2.2
3.5
2.3
3.5
2.3
3.5
2.3