Display
Cause
No rotational speed sensor signal from
primary fan.
(Flashing)
Water flow signal over specified
maximum value.
Water flow > 10 gallon/min.
(Status message).
Over-temperature detected by outlet
temperature sensor.
Temperature > 185°F
Cold water temperature sensor fault.
Backflow temperature sensor over
309°F.
The appliance will close the burner and
lock (non-volatile).
Overheat sensor (ECO) open circuit
(resets when cooler temperatures are
detected 220°F/104 °C).
Table 40
* By installer or service technician only.
830 ES
Solution
1. Disconnect power supply cord and check wire connections on back side of fan and
the two connectors on the control board, see fig. 78, page 55.
2. Check supply voltage. It must be 120VAC and properly grounded.
3. Possible defective component in fan or defective control unit call Bosch Water
Heating for further instructions.
1. Disconnect power supply cord and check wire connections on water valve and the
two connectors on the control board, see fig. 78, page 55.
2. Excessive water pressure and flow. Ensure water pressure is less than 150psi and
flow rate is below 10 gallons per minute.
1. In areas where water has a high mineral content, periodic descaling may be
necessary. See chapter7.3, page 36 for directions.
2. Check sensor (ref. page 45, chapter 10).
1. Check connector on wires coming from top of water valve for a secure connection.
See fig. 71, page 48.
2. Sensor may trip if water temperature drops below 36°F (2°C). Protect heater from
freezing conditions as any damage due to freezing conditions is not covered under
warranty.
3. Check sensor (ref. page 46, chapter 11).
1. Check inlet/outlet vent pipes.
2. Check if secondary fan connections are disconnected.
3. Check if venting specifications are met. Long vent lengths, venting with more than
three elbows, blocked vent or combination venting may cause this failure. See
chapter 4.3, page 10.
4. Call Bosch Water Heating for further instructions.
1. Disconnect power supply cord and check wire connections on the overheat sensor
(fig. 71, page 48) and the two connectors on the control board.
2. Check white wire connections at the overheat sensor. Clean terminals with an
eraser. If badly corroded, replace sensor and wire harness.
3. Check that venting specifications are met. Long vent lengths, venting with more
than three elbows, blocked vent or combination venting may cause this failure.
4. In areas where water has a high mineral content, periodic descaling may necessary,
see chapter 7.3, page 36.
5. Unplug power supply cord to the water heater. Open a hot water tap for several
minutes to allow cold water to pass through heat exchanger. Close hot water tap and
disconnect lead wires to overheat sensor. Using a multimeter, check continuity
through overheat sensor contacts. Replace sensor if open.
Problem solving | 43