Refrigeration Cycle Diagram - LG CV-H186BLB0 Service Manual

Convertible type
Table of Contents

Advertisement

Refrigeration Cycle Diagram

• CV-H186BLB0
• CV-H246BLB0
INDOOR UNIT
HEAT
EXCHANGER
MODEL
CV-H186BLB0
CV-H246BLB0
For installation over rated distance, 30g of refrigerant should be added for each meter.
ex) If 18K or 24K Model is installed at a distance of 15m, 300g of refrigerant should be added.
(15-7.5) x 30g = 225g
LIQUID SIDE
GAS SIDE
Pipe size(Diameter:ø)
Gas
Liquid
1/2"
1/4"
5/8"
1/4"
–8–
OUTDOOR UNIT
CAPILLARY TUBE
HEAT
EXCHANGER
COMPRESSOR
Piping length(m)
Rated
Max
7.5
15
7.5
20
REVERSING
VALVE
COOLING
HEATING
Elevation(m)
Rated
Max
5
8
5
8