Daikin RXYQ5PY1 Service Manual page 101

R-410a heat pump 50hz/60hz cooling only 50hz
Table of Contents

Advertisement

SiEN34-705
Air Flow Direction Setting
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to "01."
Setting Table
Setting of Air Flow Direction Adjustment
Only the model FXKQ has the function.
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Setting Table
Down-flow operation: Yes
Down-flow operation: No
Setting of Air Flow Direction Adjustment Range
Make the following air flow direction setting according to the respective purpose.
Setting Table
Air flow rate switching at discharge grille for field air flow rate switching
When the optional parts (high performance filter, etc.) is installed, sets to change fan speed for
securing air flow rate.
Follow the instruction manual for the optional parts to enter the setting numbers.
Setting of the static pressure selection (for FXDQ model)
General Information
Mode No.
First Code No.
13 (23)
1
Setting
Mode No.
13 (23)
Model No.
13 (23)
Second Code
No.
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow
Mode No.
13 (23)
First Code No.
Second Code No.
4
First Code No.
Second Code No.
5
Setting
First Code No.
Second Code No.
3
Upward (Draft
01
prevention)
02
Downward (Ceiling
03
soiling prevention)
External static pressure
01
Standard (15Pa)
02
High static pressure (44Pa)
Test Operation
01
02
Setting
Standard
95