Xc15 Start−Up And Performance Check List; Homeowner's Information − Maintenance - Lennox XC15 Series Installation Instructions Manual

Table of Contents

Advertisement

XC15 Start−Up & Performance Check List
Customer
Indoor Unit Model
Outdoor Unit Model
Notes:
START UP CHECKS
Refrigerant Type:
Rated Load Amps
Condenser Fan Full Load Amps
COOLING MODE
Suction Pressure:
Supply Air Temperature:
System Refrigerant Charge (Refer to manufacturer's information on unit or installation instructions for required sub-
cooling and approach temperatures.)
Subcooling:
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:
minus Outdoor Air Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F)
minus Supply Air Temperature (B)
Homeowner Information − Maintenance
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
1. Air Filter Ask your Lennox dealer to show you where
your indoor unit's filter is located. It will be either at the
indoor unit (installed internal or external to the cabinet)
or behind a return air grille in the wall or ceiling. Check
the filter monthly and clean or replace it as needed.
2. Disposable Filter Disposable filters should be
replaced with a filter of the same type and size.
NOTE − If you are unsure about the filter required for
your system, call your Lennox dealer for assistance.
IMPORTANT
Turn off electrical power to the unit at the
disconnect
switch
maintenance. The unit may have multiple power
supplies.
3. Reusable Filter Many indoor units are equipped
with reusable foam filters. Clean foam filters with a
mild soap and water solution; rinse thoroughly; allow
filter to dry completely before returning it to the unit or
grille.
Liquid Pressure:
Ambient Temperature:
Liquid Line Temperature (A)
Return Air Temperature (A)
before
performing
Address
Serial
Serial
Actual Amps
Actual Amps:
Return Air: Temperature:
A
A
A
NOTE − The filter and all access panels must be in
place any time the unit is in operation.
4. Electronic
equipped with an electronic air cleaner, designed to re-
move airborne particles from the air passing through
the cleaner. If your system is so equipped, ask your
dealer for maintenance instructions.
5. Indoor Unit The indoor unit's evaporator coil is
equipped with a drain pan to collect condensate
formed as your system removes humidity from the in-
side air. Have your dealer show you the location of the
drain line and how to check for obstructions. (This
would also apply to an auxiliary drain, if installed.)
Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure
of the unit to treated water (i.e., sprinkler systems,
soakers, waste water, etc.) will corrode the surface
any
of steel and aluminum parts and diminish perfor-
mance and longevity of the unit.
6. Outdoor Unit Make sure no obstructions restrict
airflow to the outdoor unit. Leaves, trash or shrubs
crowding the unit cause the outdoor unit to work harder
and use more energy. Keep shrubbery trimmed away
from the unit and periodically check for debris which
collects around the unit.
Page 19
Rated Volts
Actual Volts
B
=
SUBCOOLING
B
=
B
=
Air
Cleaner Some
IMPORTANT
APPROACH
COIL TEMP
DROP
DROP
systems
are
XC15 SERIES

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xc15-024Xc15-030Xc15-036Xc15-042Xc15-048Xc15-060

Table of Contents