For Right Rear Piping - LG LMNH122LRA0 Service Manual

Multi type air conditioner
Hide thumbs Also See for LMNH122LRA0:
Table of Contents

Advertisement

3. Art Cool Deluxe Type Indoor Unit
Connection of piping Indoor
• Preparing the indoor unit's piping and drain hose for
installation through the wall.
• Remove the plastic tubing retainer(see illustration
below) and pull the tubing and drain hose away from
chassis.
• Replace the plastic tubing holder in the original position.
(Optional)

For right rear piping

1. Route the indoor tubing and the drain hose in the
direction of rear right.
2. Insert the connecting cable into the indoor unit
from the outdoor unit through the piping hole.
• Do not connect the cable to the indoor unit.
• Make a small loop with the cable for easy
connection later.
3. Tape the tubing, drain hose, and the connecting
cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper
side can cause drain pan to overflow inside the
unit.
Drain hose
Tape
Connecting
pipe
Drain hose
Connecting cable
NOTE: If the drain hose is routed inside the room,
insulate the hose with an insulation material* so that
dripping from "sweating"(condensation) will not damage
furniture or floors.
*Foamed polyethylene or equivalent is recommended.
4. Indoor unit installation
• Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
top of the indoor unit with the upper edge of the instal-
lation plate.) Ensure that the hooks are properly seat-
ed on the installation plate by moving it left and right.
Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).
4. Connecting the pipings to the indoor unit and drain
hose to drain pipe.
• Align the center of the pipes and sufficiently tighten
the flare nut by hand.
Indoor unit tubing
• Tighten the flare nut with a wrench.
Wrench
Indoor unit tubing
Outside diameter
mm
Ø6.35
Ø9.52
Ø12.7
• When extending the drain hose at the indoor unit,
install the drain pipe.
Installation
Connecting
cable
Drain hose
Flare nut
Pipes
Open-end wrench (fixed)
Flare nut
Connection pipe
Torque
kg . m
inch
1/4
1.8
3/8
4.2
1/2
5.5
Service Manual 35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents