10-11. Thermistors

Unit Part #
Function
Failure events
Effects on the water
heater if thermistor
fails
Error codes when
thermistors fails
Diagnostic
Color/Number
of
wires
Resistance values of thermistors as a function of temperature
25.00
20.00
15.00
10.00
5.00
0.00
#407 (Inlet)
#408 (Mixing)
AOS Part #
#411 (Output)
Measures cold/hot water temperatures in the water heater.
Unable to properly measure water temperatures within the water heater.
If the thermistors fail open or short, error code appears before starting operation.
If resistance values are just off, The water heater will have temperature fluctuations
in hot water.
311 (Output)
1. Visual inspection: connection/breakage of wires and/or debris on thermistor.
2. Check voltages and resistance; proper range of values shown below.
Inlet Black(42)-Black
Output Black(12)-Black
Mixing Black(113)-Black
Insulating
20
40
60
80
510 Indoor / 510 Outdoor Service Manual
319143-085 (Inlet)
319143-190 (Mixing)
319143-096 (Output)
321 (Inlet)
68˚F (20°C) 9.0 to 13 kΩ
122˚F (50°C) 3.3 to 4.4 kΩ
176˚F (80°C) 1.4 to 1.8 kΩ
(see table below for more resistance values)
Black
Blue
Black
100
120
140
160
Temperature / ºF
27
CONFIDENTIAL
Ver. 1.00
E1 (Mixing)
Checkpoint
E2 (Output)
E3 (Inlet)
331 (Mixing)
(Inlet thermistor) 42
(Mixing thermistor) 113
(Output thermistor) 12
180
200
220