Troubleshooting by Remote Controller
Troubleshooting
Power OFF
Power ON
Power OFF
Power ON
138
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Is the stop valve open?
Are the
compressor lead
wires normal?
Are the wiring and
connection to the
compressor normal?
Is the insulation
resistance of the
compressor 100 kΩ
or less?
Compressor coils
are disconnected.
CHECK 4
Is the power transistor
normal?
Failure occurs again
after restarting the unit.
Replace the inverter PCB
(A4P).
Failure occurs again
after restarting the unit.
CHECK 4
Refer to P.182
NO
YES
NO
YES
NO
YES
YES
NO
YES
NO
NO
YES
NO
YES
NO
YES
SiBE341027
Open the stop valve.
Replace the compressor
lead wires.
Correct the wiring and
connection.
Replace the inverter
compressor.
Replace the inverter
compressor.
Replace the inverter PCB
(A4P).
Continue the operation.
(
Momentary power failure
is possible.
Continue the operation.
Replace the inverter
compressor.
Service Diagnosis