The installation location chosen must:
Comply with all clearances listed below.
Provide suitable location for the exhaust and intake venting.
Not be installed in an unheated space.
Comply with all local codes and standards.
Note: Dimensions shown are minimums. Greater clearances will simplify
installation and service.
2. 0 i n
1 5 . 8 in
8 . 0 in
FR ON TV IEW
WARNING: Do not install the boiler on carpeting
If the boiler is to be installed in an enclosed room with no fresh air intake, the room must
have proper vent louvers installed. There should be two louvers, place each within 12" of
the ceiling and floor respectively. Each vent will have a free area of 54 square inches.
Note: For boilers in an enclosed
space it is recommended to install
a CO detector in the boiler room.
When choosing an installation location insure the exhaust and intake pipes comply with
NFPA 54. The drawing on the next page illustrates the restrictions on exhaust locations.
RIVA HEAT ONLY MANUAL - REV B
10.0 i n
2.0 i n
2 7 . 7 in
Figure 6.1
1 2 .8 in
3 . 0 i n
CLOSET INST ALLA TION
MINIMU M PER MANAN T
CLEARANCE
1 8 .0 in
CLOSET IN ST ALLA TION
SERV ICECLEAR ANCE
SIDE V IEW CLOSET
IN ST ALLA TION
0 to 12"
Each opening free area =
1 sq. inch per 2,000 BTU/h
0 to 12"
Figure 6.2
Air Opening
Outside
Air Opening
15