WIRING SPECIFICATIONS

8-1. FIELD ELECTRICAL WIRING (power wiring specifications)
Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity
Main switch (Breaker)
Outdoor unit power supply
Outdoor unit power supply earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
Remote controller-Indoor unit
*1. A breaker with at least 3 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. Refer to 8-3.
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulataed by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 245 IEC 57)
3. Install an earth longer than other cables.
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line
and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is
energized. If isolator should be used between indoor unit and outdoor unit, please use 3-poles type.
1:1 system
Outdoor
unit
Unit
L
power
B
C
N
supply
S1
B Earth leakage breaker
S2
C wiring circuit breaker or
S3
isolating switch
~/N (single), 50 Hz,
*1
3 o 1.5 (Polar)
*2
*2
2 o 0.3 (Non-polar)
*3
*4
*4
*4
*4
230V
Single phase
Isolator
S1
A-Control
S2
Outdoor Unit
S3
Indoor
unit
1
Remote
controller
2
Indoor/outdoor
unit connection
cable
S1
S2
S3
RP35, 50V
RP60, 71V
~/N (single), 50 Hz,
230 V
230 V
16 A
25 A
2 o Min. 1.5
2 o Min. 2.5
1 o Min. 1.5
1 o Min. 2.5
3 o 1.5 (Polar)
1 o Min. 1.5
1 o Min. 1.5
2 o 0.3 (Non-polar)
AC 230 V
AC 230 V
AC 230 V
AC 230 V
DC 24 V
DC 24 V
DC 12 V
DC 12 V
3 poles isolator
Synchronized twin and triple system Electrical wiring
• Synchronized twin
Unit
power
B
C
supply
B Earth leakage breaker
C wiring circuit breaker or
isolating switch
• Synchronized triple
Unit
power
B
C
supply
B Earth leakage breaker
C wiring circuit breaker or
isolating switch
21
RP100, 125V
RP140V
~/N (single), 50 Hz,
~/N (single), 50 Hz,
230 V
230 V
32 A
40 A
2 o Min. 4
2 o Min. 6
1 o Min. 4
1 o Min. 6
3 o 1.5 (Polar)
3 o 1.5 (Polar)
1 o Min. 1.5
1 o Min. 1.5
2 o 0.3 (Non-polar)
2 o 0.3 (Non-polar)
AC 230 V
AC 230 V
AC 230 V
AC 230 V
DC 24 V
DC 24 V
DC 12 V
DC 12 V
S1
A-Control
S2
Indoor Unit
S3
Outdoor
Indoor
unit
unit
L
1
N
2
Indoor/outdoor
unit connection
cable
S1
S1
S2
S2
S3
S3
Outdoor
Indoor
unit
unit
1
L
Remote
controller
N
2
Indoor/outdoor
connection cable
S1
S1
S2
S2
S3
S3
RP100, 125, 140Y
3N ~ (3phase), 50 Hz,
400 V
16 A
4 o Min. 1.5
1 o Min. 1.5
3 o 1.5 (Polar)
1 o Min. 1.5
2 o 0.3 (Non-polar)
AC 230 V
AC 230 V
DC 24 V
DC 12 V
Indoor
unit
1
Remote
controller
2
S1
S2
S3
Indoor
Indoor
unit
unit
1
1
2
2
S1
S1
S2
S2
S3
S3