Caution for Assembling Outdoor Panels after Test Run

CAUTION
After replace the INV PCB assembly, make sure that connection of fan motor wires is correct.
Fan motor wire
terminal (UP)
Fan motor wire
terminal (DOWN)
If the connection between wires is incorrect, performance of the unit would be decreased.
3. Caution for Assembling Outdoor Panels after Test Run
When assemble the outdoor panels after replacement, make sure
that screws of top panel are assembled as shown figure below.
If screws are not assembled, it allows rain come into control box
causing defect of unit.
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
INV. PCB
Main PCB Case
- 47 -
to Fan moter
to Fan moter
LGE Internal Use Only