Servicing Hot Surface Igniter - International comfort products N9MSE0401410A Service And Technical Support Manual

Single stage, psc blower motor 35” tall, high efficiency condensing gas furnace
Table of Contents

Advertisement

SERVICE AND TECHNICAL SUPPORT MANUAL
Figure 9
Burner Assembly
B
S
A
URNER
UPT.
SSY
B
A
URNER
SSY
F
S
LAME
ENSOR
B
B
(
ELOW
URNER)
Representative drawing only, some models may vary in appearance.
To reinstall burner assembly:
1. Install the Hot Surface Igniter (HSI) and bracket in burner
assembly.
2. Install flame sensor on burner.
3. Align the edges of the one-piece burner with the slots in
the burner assembly and slide the burners forward until
they are fully seated in the burner assembly.
4. Align the orifices in the manifold assembly with the
support rings on the end of the burner.
5. Insert the orifices in the support rings of the burners.
NOTE: If manifold does not fit flush against the burner, do not
force the manifold on the burner assembly. The burners are not
fully seated forward in the burner assembly. Remove the
manifold and check burner positioning in the burner assembly
assembly before re-installing the manifold.
6. Attach the green/yellow wire and ground terminal to one
of the manifold mounting screws.
7. Install the remaining manifold mounting screws.
8. Check the igniter alignment. See Figure 9, Figure 10
and Figure 11.
Figure 10
Igniter Position − Top View
1-1/4-in.
(31.8)
2-1/2-in.
(64.4)
9. Attach the wires to the roll-out switches.
10. Align the burner
assembly with the openings in the
primary cell inlet panel and attach the burner assembly to
the cell panel.
11. Connect the wire for the flame sensor.
12. Connect the wire for the Hot Surface Igniter.
NOTE: Use propane-resistant pipe dope to prevent leaks. Do
not use Teflon tape.
13. Install the gas pipe to the gas valve.
440 04 4401 00
Figure 11
F
R
S
LAME
OLL−OUT
WITCH
L11F064
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of
leaks to check all connections. A fire or explosion may result
causing property damage, personal injury or loss of life.
14. Check for gas leaks with a commercially available soap
15. Turn gas on at electric switch on gas valve and at
16. Turn power on at external disconnect, fuse or circuit
17. Run the furnace through two complete heating cycles to
18. Install control door when complete.

Servicing Hot Surface Igniter

The igniter does NOT require annual inspection. Check igniter
resistance before removal. Refer to Figure 9, Figure 10 and
Figure 11.
A11405
Specifications subject to change without notice.
Igniter Position − Side View
WARNING
!
solution made specifically for the detection of leaks.
external shut-off or meter
breaker.
check for proper operation
1. Turn off gas and electrical supplies to furnace.
2. Remove control door.
3. Disconnect igniter wire connection.
4. Check igniter resistance. Igniter resistance is affected by
temperature. Only check resistance when the igniter is at
room temperature.
a. Using an ohm meter, check resistance across both
igniter leads in connector.
b. Cold reading should be between 40 ohms and 70
ohms.
5. Remove igniter assembly.
a. Using a 1/4−in. driver, remove the two screws
securing the igniter mounting bracket to the burner
assembly (See Figure 9)
b. Carefully withdraw the igniter and bracket assembly
through the front of the burner assembly without
striking the igniter on surrounding parts.
Gas Furnace: N9MSE
2−in.
50 mm
3/8−in.
9.6 mm
3/16−in.
4.6 mm
+0.8
2.5 mm
−1.5
A11620
17