B6BM, B6EM, & B6VM Series INSTALLATION INSTRUCTIONS AIR HANDLER IMPORTANT Please read all information in this manual thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit. These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance.
TABLE OF CONTENTS Important Safety Information ........3 Startup & Adjustments ..........13 Before You Start the Unit .........13 Requirements & Codes ..........3 Refrigerant Charging ..........14 General Information ...........4 Air Circulation ............14 Before You Install this Unit .........4 Running the Blower Continuously ......14 Locating the Air Handler ..........4 Selecting Continuous Low Spd Fan Operation ..
IMPORTANT SAFETY INFORMATION WARNING: INSTALLER: Please read all instructions before servicing this equipment. Pay attention to all safety warnings and PROPOSITION 65 WARNING: This product any other special notes highlighted in the manual. Safety contains chemicals known to the state of markings are used frequently throughout this manual to California to cause cancer, birth defects or designate a degree or level of seriousness and should not...
GENERAL INFORMATION Operation of Air Handler During Construction This appliance has been tested for capacity and efficiency CAUTION: in accordance with AHRI Standards and will provide many years of safe and dependable comfort, providing Failure to follow these instructions will void the it is properly installed and maintained.
and cleaned of any construction debris, and the air as the opening provided on the air handler. The ducts handler must be cleaned and/or repaired if found to should be appropriately sized to the capacity of the air be dirty, damaged, or malfunctioning in any way by handler to ensure its proper airflow rating.
handler may be used to reduce the transmission of equipment noise eminating from the air handler. These treatments can produce a quieter installation, particularly in the heated space. However, they can increase the pressure drop in the duct system. Care must be taken to maintain the proper maximum pressure rise across the air handler, temperature rise and flow rate.
Horizontal Installations to the rafters with lag bolts. The air handler can also be The B6 Series air handler can be installed horizontally in suspended using steel straps around each end of the an attic, basement, crawl space or alcove. It can also be unit.
• Refrigerant lines should be wrapped with pressure NOTE: It is recommended that the suction line be insulated up to the coil inside of the cabinet. sensitive neoprene or other suitable material where they pass against sharp sheet metal edges. 7.
Connecting the Linesets IMPORTANT NOTES FOR HORIZONTAL OR DOWNFLOW INSTALLATIONS WITH TXV VALVE: • The sensing bulb must be located flush against the suction line for optimum heat transfer. • Avoid attaching the sensing bulb to the lowest part of the suction line where condensate may accumulate.
• If the air handler is located in or above a living space 7. Wrap the refrigerant lines with pressure sensitive neoprene or other suitable material especially where where damage may result from condensate overflow, the lines enter the opening in the sheet metal. an auxiliary drain pan shall be installed under the unit.
• Use only copper wire for the line voltage power supply ELECTRICAL CONNECTIONS to this unit. Use proper code agency listed conduit and a conduit connector for connecting the supply wires to WARNING: the unit. Aluminum supply wire may be used if a heater ELECTRICAL SHOCK, FIRE OR EXPLOSION kit is installed.
fireplaces, sunlight, or lighting fixtures, and convective Control Board heat from warm air registers or electrical appliances. The control board in the air handler controls the timing Refer to the thermostat manufacturer’s instruction sheet sequence of the elements. The board is equipped with a 3 for detailed mounting and installation information.
NOTE: Variable speed air handlers cannot be twinned. STARTUP & ADjUSTMENTS Heater Kits When electric heat packages with circuit breakers are WARNING: field-installed, the circuit breaker may be used as a disconnecting means in most applications. Reference NITROGEN the NEC and local codes for disconnect requirements. HEALTH If a heater kit is installed: The B6BM air handler is shipped from the factory without...
5. Weigh in the proper amount of new (or reclaimed) energized along with a heat pump, the airflow may be higher refrigerant. Refer to the air conditioner or heat pump depending on the basic cooling/heat-pump airflow setting. installation manual for the proper type and quantity of The minimum electric heat airflow is selected by the red refrigerant.
• Terminal 4 = Hi speed • For maximum dehumidification, select an airflow near the • Terminal 5 = Med speed middle or bottom of the range for that nominal capacity. • Terminal 6 = Low speed Additional information on humidity control can be found in the Humidistat and Delay Setting sections.
UNIT MAINTENANCE CABINET SIZE FILTER SIZE Proper maintenance is most important to achieve the best 12 x 20 x 1 performance from a air handler. Some of the components 18 x 20 x 1 and their locations are shown in Figure 12 (page 18). If 20 x 20 x 1 any component of the air handler must be replaced, use Table 2.
Circuit Breaker (60A) Heating Element Assembly Transformer Motor Control Board Blower Control Upper Door Wheel Board Assembly Capacitor Motor Mount Kit Blower Housing Blower Coil Motor Assembly Filter Door Horizontal Vertical Drain Pan Drain Pan Filter Tracks Lower Door Assembly Figure 12.
ELECTRICAL DIAGRAMS & DATA 3A Fuse BLWDTC BLWDTC_R COOL HEAT LED 1 HEATER P1 Figure 13. Single Stage Control Board LED 1 HEATER P1 Figure 14. Two - Stage Control Board...
Page 24
TEST PORT EXPANSION PORT FAN SPEED 1 2 3 4 5 6 7 8 COOL HEAT STATUS BLOWER MOTOR Figure 15. Fixed Speed Motor Control Board STATUS LIGHTS L2-IN L2-OUT Y/Y2 L1-IN L1-OUT DEHUM FAN SPEED 2 3 4 5 6 7 8 TEST PORT COOL HEAT...
Page 25
RELAY Figure 17. Wiring Diagram for B6BM Series Air Handler...
Page 26
BLUE BLUE GREEN GREEN YELLOW YELLOW ORANGE ORANGE BROWN BROWN EXPANSION HEATER PLUG Figure 18. Wiring Diagram for B6EM Series Air Handler...
Page 27
WHITE BLACK 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 EXPANSION HEATER PLUG Figure 19. Wiring Diagram for B6VM Series Air Handler...
CONTROL SIGNAL & MODE OPERATION TOTAL KW BOARD ACTION Stage 1 Heat on instantly 5 KW Heat blower on after 3 second delay Stage 1 Heat on instantly 10 KW Heat blower on after 3 second delay Stage 2 Heat on after 5 seconds delay Stage 1 Heat on instantly Heat blower on after 3 second delay 15 KW...
Page 31
CONTROL SIGNAL & MODE OPERATION TOTAL KW BOARD ACTION Stage 1 Heat on instantly 5 KW Cool blower on after 3 second delay Stage 1 Heat on instantly 10 KW Cool blower on after 3 second delay Stage 2 Heat on after 5 seconds delay Stage 1 Heat on instantly Cool blower on after 3 second delay 15 KW...
INSTALLATION / PERFORMANCE CHECK LIST INSTALLER NAME: ELECTRICAL SYSTEM: Electrical connections tight? CITY: STATE: Line voltage polarity correct? _______ Supply Voltage: ____________________________ INSTALLATION ADDRESS: Has the thermostat been calibrated? CITY: STATE: Is the thermostat level? Is the heat anticipator setting correct? UNIT MODEL # UNIT SERIAL # ATTENTION INSTALLERS:...