3-20.

Installing the Drain Hose

a)
The drain hose should be slanted downward to
the outside. (Fig. 3-62)
b)
Never form a trap in the course of the hose.
c)
If the drain hose will run in the room, insulate the
hose* so that chilled condensation will not
damage furniture or floors. (Fig. 3-63)
* Foamed polyethylene or its equivalent is
recommended.
Do not supply power to the
unit or operate it until all
tubing and wiring to the
outdoor unit are completed.
Indoor
unit
Fig. 3-62
Insulation material
(locally purchased)
must be used.
Fig. 3-63
37
S4179544
Slant
Drain
hose
0082_K_I
Condensation
0083_K_I
4 4 4 4 4