Preparing to Move the Unit

Move the unit ventilator to the correct location. See Table 2, page 5
for approximate shipping weights.
Carefully remove unit ventilator from wood skid. Be sure to properly
dispose of the skid in accordance with local recycling rules and
guidelines.
Removing Unit from the Skid
Remove fasteners at each end which hold the unit to the skid and
carefully slide the front of the unit off the skid (1). Tip unit forward
until the bottom of the slotted front kickplate is resting on the floor (2).
Lift rear of unit off of the skid by tipping unit forward while supporting
the unit from the front, until it is possible to slide skid out from under
the unit. GENTLY LOWER the rear of the unit to the floor (3).
Figure 30: Removing Unit from Skid
1. Carefully slide the front of the unit off the front of the skid.
2. While supporting unit from the front, slowly tip unit forward until
bottom of kickplate is resting on floor. Lift skid slightly and GEN-
TLY lower the rear of the unit to the floor while pulling skid back
(DO NOT LET THE UNIT DROP).
Tip forward until kickplate
rests on floor
Page 16 of 42
Approx. 10"
Kickplate
Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ

Unit Ventilator Installation

Before setting the unit ventilator in position, be sure that field-supplied
electrical connections are in place, de-energized and in accordance
with the plans.

Before Sliding the Unit into Place

Sliding of this unit to the wall can be made easier with the assistance
of Caster Kit P/N 105629001 (Figures 31). A piece of cardboard placed
under the unit will make this job easier and reduce marring the floor.
(Do not leave cardboard under unit after installation.)
Be certain that the field-supplied electrical connections are in place,
de-energized and in accordance with the plans.

Installing Casters

If the unit was ordered with the optional caster wheels, install them
as follows:
1.
Remove the left and right front access panels.
2.
With the one caster (left end), ensure the caster is fully up (turn
bolt clockwise to raise, counterclockwise to lower).
3.
Locate in the left end compartment the slots and bolt location.
4.
Insert the tines of the caster channel into the slots. Securely bolt
the front to the unit front rail.
5.
Repeat for the right caster wheels (2).
6.
Slowly engage the casters by lowering the bolt. Make all caster
adjustments equally before raising the unit.
7.
When full engaged, the unit will roll forward up to the wall.
When the unit is in position, reverse the procedure and remove
the caster kit. Save the caster kit for future unit servicing or
replacement.
Figure 31: (Optional) Indoor Section Caster Installation
Raises and
lowers caster
Clockwise to raise
Left Caster
Raises and low-
ers casters (two
on compressor
end of unit)
Caster mounting cut-out
Counter-clockwise to lower
Right Caster
IM 1083