Troubleshooting by Remote Control
Mode
Function
No
Malfunction
40
hysteresis display
Display of sensor
41
and address data
Forced fan ON
43
Individual setting
44
Unit No. transfer
45
114
Contents and operation method
Display malfunction hysteresis.
The history No. can be changed with the
button.
Display various types of data.
Select the data to be displayed with the
button.
Sensor data
0: Thermostat sensor in remote control.
1: Suction
2: Liquid pipe
3: Gas pipe
Address data
4: Indoor unit address
5: Outdoor unit address
6: BS unit address
7: Zone control address
8: Cool/heat group address
9: Demand / low noise address
Manually turn the fan ON by each unit. (When
you want to search for the unit No.)
By selecting the unit No. with the
you can turn the fan of each indoor unit on
(forced ON) individually.
Set the fan speed and air flow direction by each
unit
Select the unit No. with the time mode
button.
Set the fan speed with the
button.
Set the air flow direction with the
Transfer unit No.
Select the unit No. with the
Set the unit No. after transfer with the
button.
remote control display example
Unit 1
Malfunction code
(VE007)
Sensor data display
Unit No.
Address display
Unit No.
(VE008)
Unit 1
button,
(VE009)
Unit 1
Code
button.
Fan speed 1: Low
3: High
(VE010)
button.
Unit
Code
(VE011)
SiENBE34-703
40
2-U4
Malfunction code
Hystory No: 1 - 9
1: Latest
Sensor type
41
1 1
2 7
Temperature ºC
Address type
41
1 8
1
Address
43
44
1 3
Air flow direction
P0 - P4
Present unit No.
45
1
0 2
Unit No. after
transfer
Troubleshooting