Ariston AST 100 Installation, Commissioning And User Instructions

Solarcomfort solar hot water systems solar controller

Advertisement

Quick Links

SOLARcomfort
Solar Hot Water
Systems
Installation,
AST 100 Solar
Commissioning and User
Instructions
Controller
LEAVE THESE INSTRUCTIONS WITH THE
END USER
Country of Destination GB/IE

Advertisement

Table of Contents
loading

Summary of Contents for Ariston AST 100

  • Page 1 SOLARcomfort Solar Hot Water Systems Installation, AST 100 Solar Commissioning and User Instructions Controller LEAVE THESE INSTRUCTIONS WITH THE END USER Country of Destination GB/IE...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS GENERAL INFORMATION ....2 COMMISSIONING SYSTEM ..21 1.1 G .......... 2 7.1 I ........21 UARANTEE NITIAL ETTING 1.2 S ........ 2 7.2 O YSTEM ONTENTS PTIONS FOR TANDARD YSTEM 1.3 S ....2 1 ..........23 YSTEM NSTRUCTION OOKS...
  • Page 3: General Information

    INFORMATION Please read carefully the instructions and notes about SOLARcomfort contained in this manual as they provide important information regarding the installation, commissioning and user instructions of the AST 100 Solar Controller and the SOLARcomfort system. IMPORTANT Failure to follow these instructions correctly may invalidate the guarantee.
  • Page 4: Solar Comfort

    The solar collectors are heated by the sun’s rays. The heat generated is YSTEM ORKS stored in a hot water storage cylinder e.g. an Ariston Primo twin coil stainless steel cylinder. The AST 100 Solar Controller continually compares the temperature of the water within the cylinder with the temperature of the solar collectors.
  • Page 5: Safety

    Roof mounted collectors (two collector system shown) Air vent Energy Monitoring Sensor S4 (option) Temperature Sensor S1 Ariston ITSI 210/300 twin coil cylinder AST 100 Controller PR Valve Pump group Temperature Expansion Sensor S3 vessel Upper coil heated by boiler...
  • Page 6 Regulations. All electrical work must comply with any relevant regulations that apply at the time of the installation. All electrical installation and maintenance of the AST 100 Controller must be carried out by a competent qualified installer. WARNING TYFOCOR LS Heat Transfer Fluid.
  • Page 7: Technical Data

    TECHNICAL DATA CONTROLLER Type AST100 Housing PC-ABS & PMMA Dimensions 173 x 110 x 46 Mounting Wall (2 screws) Operation 3 Push Buttons Protection IP20 / DIN 40050 Environmental Temperature 0 - 40°C FUNCTIONS Temperature Differential Control Standard Operating Hours Counter Standard Energy Monitor Option...
  • Page 8: Component List

    3.1 C Listed below are all the components supplied with the Controller. OMPONENT Item Description Controller Sensor - Collector Sensor - Cylinder Upper Sensor - Cylinder Lower Spare Fuse - T4A Cable Clips and screws Fixing Screws Wall Plug . 3.1 ONTROLLER OMPONENT 3.2 D...
  • Page 9: Regulations & Standards

    REGULATIONS & SOLARcomfort hot water heating systems should be installed in compliance with the following standards and regulations. STANDARDS 4.1 W Water Supply (Water Fittings) Regulations 1999 / www.wras.co.uk ATER EGULATIONS These regulations (bye-laws in Scotland) ensure a good supply of wholesome water and that only approved materials, pipes and fittings are used to convey water.
  • Page 10: British & European

    Connection of thermal solar heating systems 4.4 B & E RITISH UROPEAN TANDARDS EN 12976: Thermal solar heating systems and their components (prefabricated systems). ENV 12977: Thermal solar heating system and their components (bespoke systems). BS5918: Latest version: Solar heating systems for domestic hot water. Installation and equipment of DHW cylinders BS5546: 2000 Specification for installation of hot water supplies for domestic purposes, using gas-fired appliances of rated input not exceeding 70 kW.
  • Page 11: Eu Directives

    Further details available from: www.europa.eu.int 4.7 EU D IRECTIVES Construction Directive: 89/106/EEC Electromagnetic: 89/336/EEC Low voltage: 73/23/EEC Machinery Directive: 98/37/EC Preventing hot water scalding in bathrooms: using TMVs (IP 14/03). 4.8 O THER PUBLICATIONS DTI testing of solar systems (SP300275 1-3). Review of issues related to active solar heating systems (SP300246).
  • Page 12: Operation & Functions

    (The cylinder can be either a twin coil or source control. a single coil buffer type, controlled by (Upper coil shown only when it is AST 100 Controller) controlled by AST 100 Controller R2) . 5.1 AST 100 C ONTROLLER...
  • Page 13: Controller Functions

    Green Power is On - normal condition. Red/Green flashing Initialisation phase. HND1 or HND2 are set to On. INDICATOR AST 100 LIGHT Red flashing Fault condition. Indicates one of the sensors is defective or not connected. Also a sensor symbol...
  • Page 14: Controller Settings

    Navigate to the required menu option - see above. If the menu option can be changed or reset will also be displayed. INDICATOR TO CHANGE A VALUE AST 100 LIGHT Press and hold set button until flashes. BACKWARD The current setting will be displayed.
  • Page 15: System Image

    - see 7.1. System with auxiliary heat source control - Arr 2. Both coils are controlled by AST 100 (R1 & R2). Arr 1 (default) Arr 2 Typical operating display for...
  • Page 16: Tool Bar

    Solar Pump Shown in pipework to collectors. Flashes when solar pump is running (R1 On). Auxiliary Heating Pump Arr 2 only Shown in pipework to auxiliary heat source. Flashes when auxiliary pump is running (R2 On). 5.8 T The tool bar icons show the current system status. s u t i d n t a c...
  • Page 17: Operating Mode

    To display menu options use forward button to scroll forward and back button to scroll backwards. INDICATOR To change the menu option settings:- AST 100 LIGHT Press forward button to scroll through to required option. BACK If the menu option can be changed or reset will also be displayed.
  • Page 18: Installation

    ONTROLLER Fig. 6.1A gives a typical layout. The AST 100 Solar Controller should be positioned so that the householder has easy access with good visibility of the display. Also, consideration has to given to routing for connection to the pump module, cylinder and collector temperature sensors.
  • Page 19: Electrical Connections

    2(1)A 250V~. AUXILIARY HEAT SOURCE PUMP When the AST 100 is installed with an auxiliary heat source (and set as Arr 2), the pump for this is wired to the controller (R2) - see wiring diagram 6.5B.
  • Page 20: Wiring Diagram S Arr 1

    6.4 W IRING IAGRAM - Arr 1 TANDARD YSTEM IMPORTANT The mains supply cable must be separated from the sensor cables by a minimum of 15mm. Arr 1 Collector Collector S1 Collector Sensor S4 Energy Monitoring Sensor (option) FUSE 4A Temp.
  • Page 21: Wiring

    6.5 W IRING IAGRAM - Arr 2 YSTEM WITH UXILIARY EATING IMPORTANT The mains supply cable must be separated from the sensor cables by a Arr 2 minimum of 15mm. S1 Collector Sensor Collector Collector S4 Energy Monitoring Sensor (option) FUSE 4A Temp.
  • Page 22: Commissioning System

    Arr 1 Arr 1 is used when only one cylinder heat exchanger coil is controlled by the AST 100 Controller, i.e. solar system is circulated through the coil by the solar pump controlled by R1 - see wiring diagram fig. 6.4A.
  • Page 23 ‘solar day’. 2. Arr 2 Heat Circulating The lower solar coil is controlled by the AST 100 Controller, i.e. solar system is circulated through the lower coil by the solar pump controlled by R1 - see wiring diagram fig.
  • Page 24: Options For Standard Arr 1

    7.2 O The following menu options will be available when Arr is set to 1 - see 7.1 PTIONS FOR TANDARD ‘X’ indicates value is display only. Arr 1 YSTEM ‘ ‘ *indicates value can be changed using set button. Quick reference only, for further Set ‘reset’...
  • Page 25: Options For S Arr 2

    The following menu options will be available when Arr is set to 1 - see 7.1 7.3 O PTIONS FOR YSTEM WITH ‘X’ indicates value is display only. Arr 2 UXILIARY ‘ ‘ *indicates value can be changed using set button. Quick reference only, for further Set ‘reset’...
  • Page 26 The following menu options are display only. 7.4 I NFORMATION PTIONS When power is switched on to the controller it goes through an initialisation phase and then shows the first of the ‘information only’ options (COL). The forward and backward buttons can then be used to index Note through the ‘information only’...
  • Page 27 Only when Arr is 2 hP2 Displays the total hours auxiliary heat source has operated as defined by relay R2 - Auxiliary pump ON time. # # # Only when OHQM is On 7.4.6 KWh and MWh Energy Monitoring Display Only These options are only shown when Energy Monitoring OHQM function is set to ON and a sensor S4 is connected to the collector return pipework.
  • Page 28 7.5 S ETUP ARAMETERS To access the ‘setup parameters’ use the forward button to reach the PTIONS last ‘information only’ option, then press and hold the forward button Note until the first of the ‘setup parameters’ is shown (Arr). Options that display can be The forward and backward...
  • Page 29 7.5.4 S MX Maximum Cylinder Temperature S MX Range - 0.5K to 19.5K ~ Default 4.0K 4.0°K S MX is the maximum temperature the cylinder is allowed to reach. In the event of the set S MX value being exceeded, further heating of the cylinder is prohibited by switching R1 Off (solar pump stopped).
  • Page 30 7.5.8 OCF & CFR Antifreeze function OCF Range - On or Off ~ Default Off CFR Range - -10°C to 10°C ~ Default 4°C Only when OCF is On CFR is only available when OCF is set to On. When OCF is set to On and the collector temperature falls below the set 4°C CFR value the solar pump will be switched ON (R1 On).
  • Page 31 7.5.12 FMAX System Flow Rate Only when OHQM is On Range - 0 to 6.0 l/min ~ Default 6.0 l/min FMAX FMAX is only displayed when OHQM is set to On. 6.0l /min Enter the actual flow rate as set on the pump module - see fig 7.5B, also refer to Pump Manual.
  • Page 32 Relay R2 On, auxiliary heat source pump running. Indicator light flashes red/green flashes on display. Relay R2 Off, auxiliary heat source pump running. flashes on display - does not flash. 7.5.17 LANG Language Setting LANG Range - dE, En or It ~ Default En set for German set for English set for Italian...
  • Page 33: Maintenance

    The operation of the controllers Relays R1 and R2 can be checked using manual switching (HND, HND1 and HND 2) see section 7. IMPORTANT No attempt should be made to repair the controller - consult Ariston. 8.4 F The following two pages have fault finding procedures.
  • Page 34 Is the collector sensor correctly fitted/located? Does the controller switch to ‘pump On’ (R1 On)? Set Collector Check pump wiring. Refit sensor correctly. Temperature Monitoring Suspect fault with Service / replace Function (OTC) to On controller, consult pump. Ariston.
  • Page 35 Cylinders are cooled during the night. The gravitation (head) of the system may too high. Does the solar pump run during the night? Fit stronger non-return valve. Or fit electrical two way Check the controllers’ valve between the pump settings. Rever t to and the cylinder, wired default settings.
  • Page 36: User Instructions

    USER IMPORTANT INSTRUCTIONS The AST 100 Controller will have been set by the installer to reflect the system as installed. Under no circumstances should any of the system parameters be changed by the householder. The householder may reset the hour counters and energy monitor - see 9.3.
  • Page 37: Householder Reset 9.4 How To Reset C 9.5 Fault Condition

    OUNTERS Press forward button to scroll through to required option. If the menu option can be changed or reset will also be displayed. AST 100 Press and hold set button until flashes, the value will be reset BACKWARD to 0.
  • Page 38 TERMS AND CONDITIONS OF GUARANTEE The SOLARcomfort AST 100 Controller is guaranteed for 2 years. Please read these terms and conditions which are in addition to any terms and conditions detailed in this book or any registration card supplied with your appliance.