Raypak 130A Installation & Operating Instructions Manual page 12

Atmospheric above-ground pool & spa heater
Hide thumbs Also See for 130A:
Table of Contents

Advertisement

(field supplied)
Fig. 9: Gas Line Sediment Trap
NOTE: Do not use Teflon tape on gas line pipe
thread. A flexible pipe sealant suitable for LP gases
is recommended.
Gas Pressure Regulator
If adjustment is needed, remove seal and turn adjust-
ment screw clockwise to increase pressure or
counter-clockwise to decrease pressure.
Gas Pressure*
Natural Gas
Max. Inlet
10.5 in. WC
(static)
Min. Inlet
(dynamic)
Manifold Gas
3.5 in. WC
(dynamic)
*Static means without heater operating, dynamic refers to heater
operating.
Table D: Gas Pressure
(field supplied)
(field supplied)
Propane Gas
13 in. WC
7 in. WC
11 in. WC
10 in. WC
Gas Pressure Adjustment Locations
Gas Pressure Adjustment
A.
Fig. 10A: Honeywell DSI VR 8205 Gas Valve
Gas Pressure Adjustment
B.
Fig. 10B: Robertshaw MV Gas Valve
Gas Pressure Adjustment
C.
Fig. 10C: Honeywell MV Gas Valve
12