STEP 4 - Use the measured values from Step 3
to determine a target superheat of 15 degrees.
Example: Assume a suction pressure of 81
PSIG and a suction temperature of 36º F.
When the suction temperature is in line with
the suction gage pressure, the target superheat
value will be 15 degrees. (Example values high-
lighted in Table 13.2)
STEP 5 - Adjust refrigerant level to attain 15
degrees of superheat.
Add refrigerant if the suction line temperature
is above the value that is in line with the mea-
sured suction gage pressure.
1. Connect gages as shown in Step 3.
2. Purge all hoses.
3. Open bottle.
4. Stop adding refrigerant when the suc-
tion line temperature is in line with the
measured suction line pressure in Table
13.2.
Recover refrigerant if the suction line tempera-
ture is lower than the temperature that is in line
with the system's suction pressure.
28
Table 13.2
15 degree Superheat Chart
Suction Line
Suction Gage
Temp
Pressure
10
42
12
44
14
47
16
50
52
18
20
55
58
22
24
61
64
26
28
67
70
30
32
74
77
34
36
81
38
84
40
88
42
92
44
96
46
100
104
48
50
108
112
52
54
117
121
56
58
126
131
60
62
136
141
64
70
157