Control Board LEDs

The Control Board has three onboard LEDs (Figure
5) to determine the status of the unit and to assist in
troubleshooting.
Green (Diagnostic): The LED should be off in normal
operation however, if any of the 5 potential faults are
detected by the Control Board, this LED will repeatedly
blink either 1 through 5 times with a 2 second pause in
between (refer to the Green LED Blink Codes section
below).
Yellow (Audio): When lit, This LED indicates that the
Control Board is supplying approximately 10-15 VDC to
the audio signal. The audio signal should sound when
this LED is lit.
Red (Heat): When lit, this LED indicates that the
Control Board is calling for heat by supplying VDC to
terminals 3(+) and 4(-) of the Solid State Relay. When
off, it means that the grill platen is up to operating tem-
perature and satisfied

Green LED Blink Codes

Control Board
Unit State
LED Activity
The Green LED
The EEPROM memory on the Control
blinks on and off
Board is corrupted.
1 time, pauses for
2 seconds, and
repeats
The Green LED
The ambient temperature within the
blinks on and off
control compartment has exceeded 155º
2 times, pauses
F (68º C). Verify that there is proper air
for 2 seconds, and
ventilation all around the unit and that it
repeats.
is not near a significant heat source.
The Green LED
Open or disconnected Thermocouple.
blinks on and off
3 times, pauses
for 2 seconds, and
repeats.
The Green LED
The supply voltage to the unit is below
blinks on and off
160 VAC or above 265 VAC.
4 times, pauses
for 2 seconds, and
repeats.
The Green LED
The 50/60 Hz signal has been lost due
blinks on and off
to a loose, disconnected, or an open
4 times, pauses
wire harness/wiring on the AC Isolator
for 2 seconds, and
Board, or from the AC Isolator Board to
repeats.
the Control Board.
TROUBLESHOOTING (continued)
12
STATUS
GRN
Green
YELL
Yellow
RED
Red
HEAT
Figure 5. Control Board
LEDs
NOTE: During heat mode, this Red LED is very dim,
so it may be difficult to verify if the Control Board
is, or is not, calling for heat. It is recommended
that you observe the small round green LED on the
Solid State Relay (Figure 6)for mode and diagnostic
purposes. When the green LED on the Solid State
Relay is on, it means that the Control Board is call-
ing for heat. When off, it means that the Control
Board is NOT calling for heat. Typically, the VDC at
the Solid State Relay will be less than 1.0 VDC when
measured, but may vary because of different quality
VOMs. Therefore, it is recommended that you DO
NOT attempt to measure the VDC at the Solid State
Relay for diagnostic purposes.
Condition
In this state, the unit turns off the control signal to the solid
state relay and disables all front buttons and lights. The unit
will not heat up. This continues until the defaults are reloaded
into memory. To reload the defaults, turn the unit off, press and
hold the Time 2 button, turn the unit back on, and release the
button.
In this state, the unit turns off the control signal to the solid
state relay and disables all front buttons and lights. The unit
will not heat up. This continues until the ambient temperature
within the electrical compartment drops below 140º F (60º C)
and the unit is turned off and back on.
In this state, the unit turns off the control signal to the Solid
State Relay and disables all front buttons and lights. The unit
will not heat up. This continues until the Thermocouple is
reconnected or replaced, and the unit is turned off and back
on.
In this state, the unit turns off the control signal to the Solid
State Relay and disables all front buttons and front lights. The
unit will not heat up. This continues until the supply voltage is
within the proper limits and the unit is turned off and back on.
In this state, the unit turns off the control signal to the Solid
State Relay and disables all front buttons and lights. The unit
will not heat up. This continues until the 50/60 Hz signal is
reapplied and the unit is turned off and back on.
Solid State
50 AMP 24-280 VAC
2/T1
1/L1
Relay
Crouzet
TUV
Bauart
LED
.
gapruit
PRODUCT SERVICE
R
+3/A1
4/A2-
3-32 VDC
Figure 6. Solid State
Relay
P/N 1010871 Rev. D 08/05