How To Use The Vent Graph; Vertical Sidewall Applications & Installation - MHSC RFSDV24 Installation Instructions And Homeowner's Manual

Freestanding direct vent gas stove
Table of Contents

Advertisement

RFSDV24/34 Freestanding Direct Vent Gas Stove

How to Use the Vent Graph

The vent chart should be read in conjunction with the
following vent installation instructions to determine the
relationship of the vertical and horizontal dimensions of
the vent system.
1. Determine the height of the center of the horizon-
tal vent pipe exiting through the outer wall. Using
this dimension on the Sidewall Vent Graph (Fig. 8),
locate the point intersecting with the slanted graph
line.
2. From the point of this intersection, draw a vertical
line to the bottom of the graph.
3. Select the indicated dimension, and position the
stove in accordance with same.
Example A:
If the vertical dimension from the floor of the unit is 11'
(3.4m) the horizontal run to the face of the outer wall
must not exceed 14' (4.3 m).
Example B:
If the vertical dimension from the floor of the unit is 7'
(2.14m), the horizontal run to the face of the outer wall
must not exceed 8Z\x' (2.6 m).
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
3
4 5 6
7 8
9 10 11 12 13 14 15 16 17 18 19 20
Horizontal dimension from the outside face of the wall to
the center of the stove vent flange
CFM102
Sidewall vent graph showing the relationship between vertical
DV Graphic
and horizontal dimensions for a Direct Vent flue system.
9/28/00 sta
Fig. 8 Sidewall venting graph. (Dimensions in feet)
10
Example: A
Vertical Sidewall Applications
Since it is very important that the vent-
ing system maintain its balance between
the combustion air intake and the flue
gas exhaust, certain limitations as to vent
configurations apply and must be strictly
adhered to.
The vent graph showing the relationship between verti-
cal and horizontal side wall venting will help to deter-
mine the various dimensions allowable.
Minimum clearance between vent pipes
and combustible materials is one 1"
(25mm) on top, bottom and sides unless
otherwise noted.
When the vent termination exits through foundations
less than 20" (508 mm) below siding outcrop, the vent
pipe must flush up with the siding.
It is always best to locate the stove in such a way that
minimizes the number of offsets and horizontal vent
length of vent pipe from the flue collar of the stove to
the face of the outer wall.
Horizontal plane means no vertical rise exists on this
portion of the vent assembly.
The maximum number of 90° elbows per side wall
installations is three (3).
For RFSDV24 and RFSDV34 models, the maximum
horizontal rn for a minimum 12" (305 mm) vertical
rise is 3' (914 mm). (Fig. 9)
36"
(914 mm)
x
Fig. 9 Maximum horizontal run.
rev 06-02 rjs
If a 90° elbow is used in the horizontal vent run
(level height maintained) the maximum horizontal
vent length is reduced by 36" (914 mm). (Fig. 10)
This does not apply if the 90° elbows are used to
increase or redirect a vertical rise. (Fig. 11)
RFSDV24
RFSDV34
x = 12" (305 mm)
FP1495
10003550

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rfsdv34

Table of Contents