Preparation
Necessary Tools for Installation
● Drill
● Nipper
● Saw
● Hole 2 3/4
● Vacuum pump
Gas leakage detector or
soap-and-water solution
● Torque wrench
(17mm,22mm,26mm)
● Pipe cutter
● Flaring tool
● Knife
● Measuring tape
● Reamer
Drawing for the installation of indoor and outdoor units
Installation Manual of Forward Series
Procedure for Selecting the Location
Choose a place solid enough to bear the weight and vibration of the unit,where the operation noise will not be amplified.
Choose a location where the hot air discharged from the unit or the operation noise,will not cause a nuisance to the neighbors
of the user.
Avoid places near a bedroom and the like,so that the operation noise will cause no trouble.
There must be sufficient space for carrying the unit into and out of the site.
There must be sufficient space for air passage and no obstructions aroud the air inlet and air outlet.
The site must be free from the possibility of flammable gas leakage in a nearby place.
Locate the unit so that the noise and discharged hot air will not annoy the neighbors.
Install units,power cords and inter-unit cables at least 10ft away from televison and radio sets,This is prevent interference to
images and sounds.(Noise may be heard even if they are more than 10ft away depending on radio wave conditions.)
In coastal areas or other places with salty atmosphere of sulfate gas,corrosion may shorten the life of the air condition.
Since drain flows out of the outdoor unit,do not place under the unit anything which must be kept away from moisture.
NOTE: Cannot be installed hanging from ceiling or stacked.

Advertisement

loading

Summary of Contents for Haier HSU09VHJ-W

  • Page 1 Installation Manual of Forward Series Preparation Necessary Tools for Installation Procedure for Selecting the Location ● Drill ● Choose a place solid enough to bear the weight and vibration of the unit,where the operation noise will not be amplified. ● Nipper ●...
  • Page 2: Indoor Unit

    [ Left Left-rear piping ] Accessory parts In case of left side piping, cut away, with a nipper, the lid for left piping. In case of left-rear piping, bend the pipes according to the piping direction to Drain hose (1) Remote controller (1) the mark of hole for left-rear piping which is marked on heat insulation materials.
  • Page 3: Outdoor Unit

    Ensure that no dirt or debris enters the pipe. Outdoor unit The standard pipe length is 7m (27 9/16) . If it is over 7m (27 9/16) , the function of the unit will be affected. If the pipe has to be lengthened, the refrigerant should Indoor uni t be charged, according to 20 g/m (0.018 oz/inch).
  • Page 4 No gas leakage? On Drainage In case of gas leakage, tighten parts of pipe connection. If leakage stops, Please install the drain hose so as to be downward slope without fail. then proceed step 6. If leak continues, remove the refrigerant used for the Please don’t do the drainage as shown below.

This manual is also suitable for:

Hsu18vhj-wHsu18vhj(db)-wHsu24vhj-wHsu09vhj(db)-wHsu12vhj-wHsu12vhj(db)-w ... Show all