If replacing a condensing unit or air handler, the system must
be manufacturer approved and Air Conditioning, Heating and
Refrigeration Institute (AHRI) matched. NOTE: Installation of
unmatched systems is not allowed.
Operating the unit in a structure that is not complete (either as
part of new construction or renovation) will void the warranty.

Installation Clearances

Special consideration must be given to location of the con-
densing unit(s) in regard to structures, obstructions, other units,
and any/all other factors that may interfere with air circulation.
Where possible, the top of the unit should be completely unob-
structed; however, if vertical conditions require placement be-
neath an obstruction there should be a minimum of 60
inches between the top of the unit and the obstruction(s).
The specified dimensions meet requirements for air circulation
only. Consult all appropriate regulatory codes prior to deter-
mining final clearances.
Another important consideration in selecting a location for the
unit(s) is the angle to obstructions. Either side adjacent the
valves can be placed toward the structure provided the side
away from the structure maintains minimum service clearance.
Corner installations are strongly discouraged.
NOT
RECOMMENDED
B
A
AA
C
AA
AA
A
C
Minimum Airflow C learance
Model Type
R esidential
Light C ommercial
This unit can be located at ground floor level or on flat roofs. At
ground floor level, the unit must be on a solid, level foundation
that will not shift or settle. To reduce the possibility of sound
transmission, the foundation slab should not be in contact with
or be an integral part of the building foundation. Ensure the
foundation is sufficient to support the unit. A concrete slab
raised above ground level provides a suitable base.

Rooftop Installations

If it is necessary to install this unit on a roof structure, ensure
the roof structure can support the weight and that proper con-
sideration is given to the weather-tight integrity of the roof. Since
B
B
B
AA
C
AA
AA
AA
C
A
B
C
10"
10"
18"
12"
12"
18"
the unit can vibrate during operation, sound vibration transmis-
sion should be considered when installing the unit. Vibration
absorbing pads or springs can be installed between the con-
densing unit legs or frame and the roof mounting assembly to
reduce noise vibration.
NOTE: These units require special location consideration in
areas of heavy snow accumulation and/or areas with prolonged
continuous subfreezing temperatures. Heat pump unit bases
have cutouts under the outdoor coil that permit drainage of
frost accumulation. Situate the unit to permit free unobstructed
drainage of the defrost water and ice.
In more severe weather locations, it is recommended that the
unit be elevated to allow unobstructed drainage and air flow.
The following elevation minimums are recommended:
Design Temperature
+15° and above
-5° to +14°
below -5°

Safe Refrigerant Handling

While these items will not cover every conceivable situation,
they should serve as a useful guide.
WARNING
To avoid possible injury, explosion or death, practice
safe handling of refrigerants.
WARNING
OK!
Refrigerants are heavier than air. They can "push out"
OK!
the oxygen in your lungs or in any enclosed space.To
avoid possible difficulty in breathing or death:
• Never purge refrigerant into an enclosed room or
space. By law, all refrigerants must be reclaimed.
• If an indoor leak is suspected, throughly ventilate the
area before beginning work.
OK!
• Liquid refrigerant can be very cold. To avoid possible
OK!
frostbite or blindness, avoid contact and wear gloves
OK!
OK!
and goggles. If liquid refrigerant does contact your
skin or eyes, seek medical help immediately.
• Always follow EPA regulations. Never burn refrig-
erant, as poisonous gas will be produced.
WARNING
To avoid possible explosion:
• Never apply flame or steam to a refrigerant cylinder.
AA
If you must heat a cylinder for faster charging,
20"
partially immerse it in warm water.
24"
• Never fill a cylinder more than 80% full of liquid re-
frigerant.
• Never add anything other than R-22 to an R-22 cy-
linder or R-410A to an R-410A cylinder. The service
equipment used must be listed or certified for the
type of refrigerant used.
• Store cylinders in a cool, dry place. Never use a cy-
linder as a platform or a roller.
2
Suggested Minimum Elevation
2 1/2"