Product version: 1.2
Table 8. Electromagnetic compatibility tests
Description
Electrostatic discharge test:
• Contact discharge
• Indirect contact discharge
Conducted RF Immunity test:
• 150 kHz...80 MHz
Radiated RF Immunity test:
• 80...1000 MHz
• 1400...2000 MHz
• 2000...2700 MHz
Fast transient disturbance tests:
• Communication ports
• AC power input ports
Surge immunity test:
• AC power input ports
Voltage dips and short interruptions
Emission tests:
• Conducted
0.15...0.50 MHz
0.50...30 MHz
• Radiated
30...230 Mhz
230...1000 MHz
Table 9. EMC compliance
Description
Standard
ABB
Type test value
4 kV
4 kV
10 V (rms)
10 V/m (rms)
3 V/m (rms)
1V/m (rms)
1 kV
2 kV
2 kV, line-to-earth
1 kV, line-to-line
0 % / 1 cycle
40 % / 10 cycles
70 % / 25 cycles
< 79 dB(µV) quasi peak
< 66 dB(µV) average
< 73 dB(µV) quasi peak
< 60 dB(µV) average
< 50 dB(µV/m) quasi peak,
measured at 3 m distance
< 58 dB(µV/m) quasi peak,
measured at 3 m distance
Reference
ETSI EN 301489-1 (V1.8.1 2008-04)
IEC 61000-6-1 (Second edition 2005–01)
IEC 61000-6-3 (2006–07)
1MRS757424 C
Reference
EN 61000-4-2
EN 61000-4-6
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-11
CISPR 22 (EN 55022), Class B