Address Reported Problems; Inspect Water Heater Interior; Check All Piping For Leaks; Clean Condensate Trap - Lochinvar 151 - 801 Service Manual

Outdoor armor water heater
Hide thumbs Also See for 151 - 801:
Table of Contents

Advertisement

2
Maintenance
Follow the service and maintenance procedures given throughout this manual and in component literature
WARNING
shipped with the water heater. Failure to perform the service and maintenance could result in damage to
the water heater or system. Failure to follow the directions in this manual and component literature could
result in severe personal injury, death, or substantial property damage.
The water heater should be inspected annually only by a qualified service technician. In addition, the
WARNING
maintenance and care of the water heater designated in Table 2A and explained on the following pages must
be performed to assure maximum water heater efficiency and reliability. Failure to service and maintain the
water heater and system could result in equipment failure.
Electrical shock hazard – Turn off power to the water heater before any service operation on the water
WARNING
heater except as noted otherwise in this instruction manual. Failure to turn off electrical power could result
in electrical shock, causing severe personal injury or death.

Address reported problems

1. Inspect any problems reported by the owner and correct
before proceeding.
Inspect water heater area
1. Verify that water heater area is free of any combustible
materials, gasoline and other flammable vapors and
liquids.
2. Verify that air intake area is free of any of the contaminants
listed in Section 1 of the Outdoor Armor Water Heater
Installation and Operation Manual. If any of these are
present in the water heater intake air vicinity, they must
be removed.

Inspect water heater interior

1. Remove the front access cover and inspect the interior of
the water heater.
2. Vacuum any sediment from inside the water heater and
components. Remove any obstructions.

Clean condensate trap

1. Inspect the condensate drain line, condensate PVC
fittings, and condensate trap.
2. Remove the PVC cap retaining screw from the PVC cap
(FIG. 2-1).
3. Remove the 2 inch PVC cap with the switch located at the
top of the trap (FIG. 2-1).
4. Remove any sediment in the trap.
5. Fill with fresh water until the water begins to pour out of
the drain.
6. Replace the cap. Press the cap onto the trap until the cap
makes contact with the drain.
7. Replace the retaining screw.
20
Outdoor Armor Water Heater Service Manual
Figure 2-1 Condensate Trap
RETAINING SCREW
CONDENSATE FROM
HEAT EXCHANGER
The condensate trap must be filled with water
WARNING
during all times of water heater operation to
avoid flue gas emission from the condensate
drain line. Failure to fill the trap could result
in severe personal injury or death.

Check all piping for leaks

Eliminate all system or water heater leaks.
WARNING
Leaking water may cause severe property
damage.
1. Inspect all water and gas piping and verify to be leak free.
2. Look for signs of leaking lines and correct any problems
found.
3. Check gas line using the procedure found in Section 4
- Gas Connections of the Outdoor Armor Water Heater
Installation and Operation Manual.
2" PVC CAP WITH
BLOCKED DRAIN SWITCH
1/2" (12.7mm) PVC ELBOW
( FIELD SUPPLIED)
TO FLOOR DRAIN
IMG00846

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

151200286400501601 ... Show all

Table of Contents